2-14
BE1-BPR Application
either provide a separate path to a single trip coil or be hooked to the backup trip coil if available.
6.
Alarm Output. An Alarm output is provided to signal relay failure or diagnostic alarm.
Breaker Failure Logic 2 For Standard Relays (BFL2)
BFL2 logic provides the following application features:
1.
Three-Pole Tripping BF Logic (Features: Output latch-in provided and Control timer limits operational
window). Three BFI inputs are available at IN3, IN4, and IN5 to start delay timer T1. If the BFI inputs
are not reset by the time timer 1 times out and either the phase (F1) or neutral (F2) fault detector is
picked up, BFO1-3 will close (OUT1-3), tripping the backup breakers. A control timer (T3) is used to
limit the breaker failure window of opportunity. Refer to the breaker failure timing diagram in Section 1
for information on setting the delay and control timers.
2.
Single-Pole Tripping BF Logic (Features: Output latch-in provided and Control timer limits operational
window). If single-pole tripping is used, two additional BFI inputs are available (IN6 and IN7) to start
delay timer T2. These inputs are only supervised by the phase fault detector (F1). If the BFI (IN6 and
IN7) inputs are not reset by the time the timer T2 times out and the phase fault detector (F1) is still
picked up, the BFO outputs (OUT1-3) will close, tripping the backup breakers. Control timer, T3 is used
to limit the breaker failure window of opportunity. Refer to the breaker failure timing diagram in Section
1 for information on setting the delay and control timers.
Neutral fault detector F2 is not used to supervise the single-pole BF logic because F2 is still picked up
by the phase imbalance after the fault clears. Three-phase BF logic is inhibited during this period
because there is no 3-phase BFI input active. For single-pole tripping, the phase pickup (PU1) must be
set above maximum load levels.
3.
Trip Coil Status Monitor. Preprogrammed logic is provided using IN1 to provide breaker status and IN2
Summary of Contents for BE1-BPR
Page 31: ...BE1 BPR Application 2 17...
Page 42: ...3 4 BE1 BPR Human Machine Interface Figure 3 4 BE1 BPR Relay Vertical Mount Front View...
Page 43: ...BE1 BPR Human Machine Interface 3 5 Figure 3 5 BE1 BPR Relay Vertical Mount Rear View...
Page 49: ...4 6 BE1 BPR Functional Description Figure 4 2 Enhanced BE1 BPR Menu Display Screens...
Page 50: ...BE1 BPR Functional Description 4 7 Figure 4 3 Standard BE1 BPR Menu Display Screens...
Page 94: ...5 4 BE1 BPR BESTlogic Figure 5 1 BESTlogic Function Blocks...
Page 121: ...BE1 BPR Installation 7 3 Figure 7 3 Overall Dimensions Vertical Mount...
Page 122: ...7 4 BE1 BPR Installation Figure 7 4 Overall Dimensions Side View Vertical Mount...
Page 123: ...BE1 BPR Installation 7 5 Figure 7 5 Panel Drilling Diagram Vertical Mount...