2-20
BE1-BPR Application
6.
Retrip Output. A retrip output is provided to give a backup trip signal to the breaker trip coil. This can
either provide a separate path to a single trip coil or be hooked to the backup trip coil if available.
7.
External Fault Trigger. The enhanced BE1-BPR relay provides the ability to save the COMTRADE fault
records for twelve events in memory at one time. An external fault trigger is provided to allow other
multiple units to record the same event.
8.
Alarm Output. An alarm output is provided to signal relay failure or diagnostic alarm.