9365200990 Rev F
BE1-CDS240 General Information
1-3
Each output is programmable using BESTlogic (assign any virtual output to any physical output
relay) and can be given a user meaningful name for the variable and for each state (open and
closed) for use in reporting functions.
Output logic can be overridden to open, close or pulse each output contact for testing, or control
purposes.
Protection and Control Functions
Setting Groups
Four (4) settings groups allow adaptive relaying to be implemented to optimize the relay settings
for various operating conditions.
Automatic and external logic can be employed to select the active setting group.
Differential Protection
Three-phase percentage restrained differential protection with harmonic restraint: 87. Protection
can be set to monitor two, three, or four windings. Unused inputs can be used for overcurrent
protection.
Two restricted earth fault ground differential protection elements with independent ground (IG)
input (and C-phase, IG2, of Current Circuit 4): 87ND and 187ND.
Tap compensation for the differential protection can be automatically calculated by the relay
based upon user settings of CT ratio, MVA and kV base values.
Ground differential between calculated residual of any winding and the phase C current input of a
fourth and unused winding (IG2).
Each winding can be independently set for a phase relationship (relative to winding 1) of 0 to 360
degrees in steps of 30 degrees.
Each winding can be set for IEC standard transformer connections.
Overcurrent Protection
Instantaneous overcurrent with settable time delay for each operating quantity (A, B, C, N (using
IN or IG) and Q. Eight (8) sets Phase, Five (5) sets Neutral, Four (4) sets Negative-Sequence.
Each function is individually assignable to any of the current input circuits. Functions are: 50TP,
150TP, 250TP, 350TP, 450TP, 550TP, 650TP, 750TP, 50TN, 150TN, 250TN, 350TN, 450TN,
50TQ, 150TQ, 250TQ, and 350TQ.
Inverse time overcurrent functions with integrating or instantaneous reset. Four (4) for Phase, five
(5) for Neutral, and four (4) for Negative-Sequence. Each function is individually assignable to
any of the current input circuits. Functions are 51TP, 151TP, 251TP, 351TP, 51TN, 151TN,
251TN, 351TN, 451TN, 51TQ, 151TQ, 251TQ, and 351TQ.
Time overcurrent functions employ a dynamic integrating timing algorithm covering a range from
pickup to 40 times pickup with selectable instantaneous or integrated reset characteristics.
Time overcurrent curves conform to IEEE PC37.112 and include seven curves similar to
Westinghouse/ABB CO curves, five curves similar to GE IAC curves, four IEC curves, a fixed
time curve, and a user programmable curve.
Digital signal processing filters out unwanted harmonic components while providing fast
overcurrent response with limited transient overreach and overtravel.
Voltage Protection
Voltage control or restraint for 51P (51V protection)
One (1) volts per hertz protective element (24) provides overexcitation protection for a generator
and/or transformer.
Two phase (2) undervoltage elements, 27P and 127P, provide phase undervoltage protection.
Two phase (2) overvoltage elements, 59 and 159, provide phase overvoltage protection.
One (1) negative-sequence overvoltage element (47) provides protection for phase unbalance or
a reverse system phase-sequence.
One (1) zero sequence overvoltage element (59X) provides protection for ground faults on
ungrounded systems using calculated 3VO.
Frequency Protection
Six (6) over/underfrequency protection elements are provided: 81, 181, 281, 381, 481, and 581.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......