SECTION 8
APPLICATION
INTRODUCTION
This section discusses the application of the BE1-CDS240 Current Differential System using a
preprogrammed logic scheme. The CDS240 has one embedded, default logic scheme (CDS240-BATX-A-
BE) as delivered from the factory. This scheme was developed based on customer requirements, input
from Basler Electric Application Engineers, and on IEEE C37.91 Guide for Protective Relay Applications
to Power Transformers. Other preprogrammed logic schemes such as Basic Differential, Basic
Transformer with Control Logic, Basic Transformer with Backup Logic, Bus Protection with Backup Logic,
and Motor Protection are available on the Basler Web site and included in the logic library of
BESTCOMS, Basler Electric's Windows based graphical user interface program. A description of each of
those schemes follows the Basic Transformer discussion. The paragraphs on
Details of Preprogrammed
Logic
describe the characteristics of the logic scheme and how they combine to create a Transformer
Differential Scheme for application on network and radial transformers at any voltage level. A detailed
description of the preprogrammed scheme is also provided. This section concludes with tips on
programming custom logic schemes to meet specific user applications.
This preprogrammed logic scheme is designed to take advantage of all the CDS240 protection
capabilities. However, not all elements have to be set. The protection engineer can choose which
elements receive operational settings or adapt the scheme to user specific needs by changing the
protection and control elements and settings. In many cases, this eliminates the need to create a custom
logic scheme from scratch.
Please note that this preprogrammed logic scheme also illustrates typical ways of using or controlling
various functions. The user may choose to create a custom logic scheme by mixing preprogrammed logic
with user defined logic. The logic also can be modified to incorporate some of the features described in
the
Application Tips
provided at the end of this section. The flexibility of BESTlogic in combination with
easy to use BESTCOMS allows the engineer to quickly create a protection and control scheme that
meets the exact requirements of the application.
CAUTION
If "NONE" logic is selected, the protection elements are not connected to the
virtual outputs or output relays, and fault recording features including targets are
not enabled. The user will have to program and enable these features and
functions as part of building a custom logic scheme.
EXPLANATION OF TERMS
Understanding the following terms and definitions will help to clarify the application discussions that
follow:
Function Element
Stand-alone protection or control function that is equivalent to the discrete component counterpart.
Virtual Switches
Virtual switches are logic switches that emulate traditional protection and control panel switches such as
the breaker control switch (101) and on/off, selector switches (43). Virtual switches may be operated via
the ASCII command interface or the front panel human-machine interface (HMI). Operation of these
switches can be password protected or disabled if the user chooses not to use them. You might do this
when using a preprogrammed logic scheme without changing the preprogrammed logic.
9365200990 Rev F
BE1-CDS240 Application
8-1
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......