BE1-CDS240 Application
8-23
State Labels
Output Purpose
Description
Label
True False
VO13
Alarm to indicate that differential
cutoff switch operation is being
blocked. This can be used as a
programmable alarm by enabling
alarm point 21. The programmable
Variable Label will be displayed on
the alarm report when TRUE.
VO13 is TRUE when
Virtual Switch 243 is in
the TRUE position.
87-BLOCKED ACTIVE NORMAL
BESTlogic Expression: VO13=243
VO14
Optional. Use to annunciate an
alarm when alarm point 22 is
enabled.
VO14 is TRUE when
IN7 is TRUE.
IN7-ALARM ACTIVE
NORMAL
BESTlogic Expression: VO14=IN7
VO15
Optional. Use to annunciate an
alarm when alarm point 23 is
enabled.
VO15 is TRUE when
IN8 is TRUE.
IN8-ALARM ACTIVE
NORMAL
BESTlogic Expression: VO15=IN8
Table 8-18. CDS240- TXCL-B-BE Hardware Output Logic
Output Purpose
Description
OUTA
Relay Trouble Alarm.
OUTA contact closes when relay trouble alarm occurs.
BESTlogic Expression: OUTA=VOA
OUT1
Phase differential trip. OUT1 is a
high-speed trip contact.
OUT1 contact closes if restrained, unrestrained, 51, or 151 trip
occurs.
BESTlogic Expression: OUT1=VO1
OUT2
Breaker 1 Trip.
OUT2 contact closes if restrained, unrestrained, 51, 151, or 43
virtual switch trip occurs.
BESTlogic Expression: OUT2=VO2
OUT3
Breaker 1 Close.
OUT3 contact closes if virtual control switch is TRUE and 86
lockout is not tripped.
BESTlogic Expression: OUT3=VO3
OUT4
Breaker 2 Trip.
OUT4 contact closes if restrained, unrestrained, or any 251 time
overcurrent trip occurs, or 101T (tripped) is TRUE.
BESTlogic Expression: OUT4=VO4
OUT5
Breaker 2 Close.
OUT5 contact closes if breaker control switch 101C is TRUE
(closed) and 86 lockout is not tripped.
BESTlogic Expression: OUT5=VO5
OUT6
Used to annunciate an alarm.
OUT6 contact closes when any programmed major alarm
condition is TRUE.
BESTlogic Expression: OUT6=VO6
OUT7 -
14
Spare output contacts.
N/A
BESTlogic Expression: OUT7-14 =0
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......