9365200990 Rev F
BE1-CDS240 Application
8-33
Output Purpose
Description
OUT3
Breaker 2 failure trip. (86F for
example).
OUT3 closes when BFT or 62 times out.
BESTlogic Expression: OUT3=VO3
OUT4
Breaker 2 Trip.
OUT4 contact closes 87R or 87U trip output of the phase
differential protection function is TRUE. Or for 251 bus backup
overcurrent trip. Or for control switch trip. Or when BF is initiated.
BESTlogic Expression: OUT4=VO4
OUT5
Breaker 2 Close.
OUT5 contact closes when virtual control switch is TRUE and
86T or 86B LO is not tripped.
BESTlogic Expression: OUT5=VO5
OUT6
Signal relay on bus source that is
using BUS logic that a feeder
relay is out of service.
OUT6 contact closes when Feeder relay is out of service as
indicated by contact open from the feeder relays.
BESTlogic Expression: OUT6=VO6
OUT7 -
14
Spare output contacts.
N/A
BESTlogic Expression: OUT7-14 =0
CDS240-BSBU-A-BE (BUS WITH BACKUP) LOGIC SCHEME
The BUS With Backup (CDS240-BSBU-A-BE) scheme was designed to provide low impedance, high-
speed phase, and ground bus fault protection for distribution buses. This scheme also includes a high-
speed bus-interlocking scheme that provides a second level of bus protection and "Feeder Relay Out of
Service” backup protection. Figure 8-10 shows the interconnection of a BE1-CDS240 (CDS240-TXBU-B-
BE) for backup protection, a BE1-851 or BE1-951 for feeder protection, and the BE1-CDS240 for bus
protection. When interconnected with feeder relays using preprogrammed feeder logic (FDR-W-IL), the
CDS240-BSBU-A-BE scheme provides complete backup, except for reclosing, for the feeder relays if
relay failure occurs or when they are out of service for testing or maintenance. Virtual control switch logic
is used for local or remote (SCADA) control and can be used to replace the equivalent panel control
switches.
The control switch elements are referred to as virtual because they have no physical form, they exist only
in logic form, and they can only be operated via the ASCII command interface or the front panel. The
Virtual 101 Switch is used to trip and close the bus main breaker, Virtual Control Switch 43 is used to turn
off the 87 protection element and 743 is used to select test mode enable. The user may choose to
eliminate the use of external switches, as the virtual switches are fully functional equivalents of their
physical counterparts.
Figure 8-11 is a one-line drawing and Figure 8-12 is a logic drawing. Both represent the logic settings
shown in Table 8-25. In Table 8-25, the user can see the protection and control elements that are
enabled for the CDS240-BSBU-A-BE application and how the elements are logically wired together
(equations). If the user should decide to build on this scheme, all elements required for a more detailed
application are available through programming. For programming details, refer to Section 7,
BESTlogic
Programmable Logic.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......