Virtual control switch elements enabled for use in this scheme are 101, 43, and 743. The 101 Control
Switch trips the low-side breaker through output 4 and closes the low-side breaker through Output 5.
Control Switch 43 is used to turn the 87 function on or off and 743 us used to enable Test Mode.
Test Mode
When Virtual Control Switch 743 is enabled, breaker failure initiate through Output 6 is defeated.
Setting Group
For normal operation, setting group 0 is active for the CDS240-BSBU-A-BE scheme. IN7 to the BE1-
CDS240 identifies when a feeder relay (851) is out of service. At the same time, IN5 of the transformer
BE1-CDS240 scheme gets the same signal. Both relays then switch to setting group 1. Setting group
selection mode 2, binary coded selection, is used to recognize the group setting state. When input D0 to
the setting group selection element is a one, it is interpreted as a binary 1 causing the logic to switch to
group 1.
When the bus BE1-CDS240 is in setting group 1, it is operating in feeder backup mode. This expression
is programmed to Virtual Output 14 that drives alarm bit #22 in the programmable alarm mask. It can be
masked to drive an alarm LED and alarm display to indicate when the relay is in feeder backup mode and
to trip a feeder breaker instead of the bus breaker.
Alarms
Three logic variables drive the front panel LEDs: Relay Trouble (ALMREL), Major Alarm (ALMMAJ), and
Minor Alarm (ALMMIN). A fourth logic variable, Logic Alarm (ALMLGC), has no associated front panel
LED. When the relay self-test detects a problem in the relay (ALMREL) as programmed for the CDS240-
BSBU-A-BE scheme, the Relay Trouble LED lights, Output A operates and all outputs are disabled.
When a Major Alarm is detected (ALMMAJ), the associated LED lights, but in this scheme, no output
relay is programmed to operate. When a Minor Alarm (ALMMIN) is detected, the associated LED lights,
but in this scheme, no output relay is programmed to operate.
Table 8-26. CDS240-BSBU-A-BE Contact Input Logic
State Labels
Input Purpose Name
Label
Energized De-Energized
IN1
Optional input. Used for CT input circuit 1 breaker
status indication in SER reports. TRUE when
breaker is closed.
BREAKER-1 CLOSED
OPEN
NOTE
Tables 8-26 through 8-30 provide detailed logic definitions for the inputs, outputs,
protection, and control elements. Only those inputs, logic blocks, virtual switches,
and outputs in use for the CDS240-BSBU-A-BE preprogrammed logic are
described in the following tables.
CAUTION
Test Mode Enable does not defeat the trip outputs of the relay. External trip test
blades must be opened or the CDS240-BSBU-A-BE logic scheme must be
modified to suit the user's test mode requirements. One option is to trip the
breakers through an 86 device only. Typically, 86 devices are installed with test
blades in the breaker trip circuit so that the protection scheme can be safely
operational checked while the primary equipment is in service. Another option is
to inhibit all trip outputs when test mode is enabled. However, external devices
such as auxiliary relays and 86 devices would no longer be included in the
operational test.
9365200990 Rev F
BE1-CDS240 Application
8-39
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......