8-40
BE1-CDS240 Application
9365200990 Rev F
State Labels
Input Purpose Name
Label
Energized De-Energized
IN3
Used for 86 status indication in SER reports.
TRUE when Transformer 86 tripped. Also blocks
virtual breaker close switch close until 86 is reset.
86T-TRIPPED TRIPPED
NORMAL
IN4
Optional Input. Used for 86B status indication and
locks out the low-side breaker when TRUE.
TRUE when 86B is tripped.
86B-TRIPPED TRIPPED
NORMAL
IN5
Block instantaneous when feeder relay is picked
up. Feeder relays such as BE1-851 or BE1-951
using one of the preprogrammed schemes with
interlock logic.
FDR-RLY-
PICKEDUP
PICKDUP NORMAL
IN7
Signal from relay on bus source that is using
BACKUP logic that a feeder relay is out of
service. BE1-851, BE1-951, or BE1-CDS240
using preprogrammed logic scheme BACKUP.
BACKUP-
FDR-RELAY
BACKUP NORMAL
IN8
Puts the relay in test mode so that the breaker
failure is disabled when Input 8 is de-energized.
TEST-MODE-
DISABL
NORMAL TSTMODE
Table 8-27. CDS240-BSBU-A-BE Function Block Logic
Function Purpose
BESTlogic
Expression
Mode
Setting
87
Used for percent-restrained differential protection with high-speed
unrestrained instantaneous differential protection. Differential function
is blocked when Virtual Switch 43 is TRUE.
43 1
(enabled)
51P
Applied to bus main (CT 1). Normally for bus time OC protection
coordinated with feeder relay time OC. When in feeder relay backup
mode, provides primary time OC protection for feeder. SG1 settings
must coordinate with other feeder 51 elements.
0
1 (Circuit 1)
51N
Applied to bus main (CT 1). Normally for bus time OC protection
coordinated with feeder relay time OC. When in feeder relay backup
mode, provides primary time OC protection for feeder. SG1 settings
must coordinate with other feeder 51 elements.
0
1 (Circuit 1)
51Q
Applied to bus main (CT 1). Normally for bus time OC protection
coordinated with feeder relay time OC. When in feeder relay backup
mode, provides primary time OC protection for feeder. SG1 settings
must coordinate with other feeder 51 elements.
0
1 (Circuit 1)
151P
Applied to bus main (CT 1). Used for backup bus time OC trip.
Provides primary time OC protection when 51 elements are used for
feeder relay backup.
0
1 (Circuit 1)
151N
Applied to bus main (CT 1). Used for backup bus time OC trip.
Provides primary time OC protection when 51 elements are used for
feeder relay backup.
0
1 (Circuit 1)
151Q
Applied to bus main (CT 1). Used for backup bus time OC trip.
Provides primary time OC protection when 51 elements are used for
feeder relay backup.
0
1 (Circuit 1)
50TP
Applied to bus main (CT 1). Normally for fast bus OC protection (2-4
cycles delay) as backup to 87. When in feeder relay backup mode,
provides near instantaneous for feeder. Block when feeder relay is
picked up indicating that the fault is on a feeder.
IN5
1 (Circuit 1)
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......