8-50
BE1-CDS240 Application
9365200990 Rev F
Function Purpose
BESTlogic
Expression
Mode
Setting
251P
This element protects for a jam condition. It is blocked while the
motor is starting as determined by VO8.
VO8
1 (Circuit 1)
50TP
50TP is used for motor start detection (50S). Target should not be
enabled with the SG-TARG setting for this function.
0
1 (Circuit 1)
50TN
50TN is used for ground fault backup protection.
0
1 (Circuit 1)
50TQ
50TQ is used for loss of phase detection.
0
1 (Circuit 1)
150TP
This element provides LR protection for low inertia motors. It is
blocked when the motor is running (after the 250TP time setting
expires) or when the high inertia mode is selected.
243
1 (Circuit 1)
250TP
The 250TP is used to detect when the motor is running. It supervises
the 150TP locked rotor protection for low inertia motor applications
and the 251P jam protection. Target should not be enabled with the
SG-TARG setting for this function.
0
1 (Circuit 1)
Table 8-34. CDS240-MOTR-A-BE Virtual Switch Logic
State Labels
Switch Purpose
Mode
Label
True False
143
Speed Switch selector. When enabled, the
motor starting is determined by speed
switch. When None, starting is determined
by current detector set at 85% of locked
rotor current.
2 (On/Off)
SPEED-SWITCH
ENABLED
NONE
243
Selector Switch to customize the protection
for high or low inertia applications. When
high is selected, blocks 150TP and enables
151P for locked rotor protection.
2 (On/Off)
INERTIA-MODE
HIGH
LOW
Table 8-35. CDS240-MOTR-A-BE Virtual Output Logic
State Labels
Output Purpose
Description
Label
True False
VOA
Relay Trouble Alarm.
VOA TRUE if relay trouble alarm
occurs.
RELAY-
TROUBLE
ACTIVE NORMAL
BESTlogic Expression: VOA=0
VO1 Breaker
trip.
TRUE when protective trip
expression is TRUE.
MOTOR_TRIP TRIP NORMAL
BESTlogic Expression: VO1=VO11
VO4
VO4 TRUE, Overload
protection (51P) is
picked up and timing
to trip.
TRUE when Overload protection
(51P) is picked up and timing to trip.
OVERLOAD ALARM
NORMAL
BESTlogic Expression: VO4=VO14
VO5
Unbalance alarm
output contact.
VO5 TRUE, Unbalance protection
(51Q) is picked up and timing to trip.
UNBALANCE TRIP NORMAL
BESTlogic Expression: VO5=VO15
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......