11-22
BE1-CDS240 ASCII Command Interface
9365200990 Rev F
RT
Command
Purpose:
Read Transformer Duty Status
Syntax:
RT
Example:
RT
Reference:
Section
6,
Reporting and Alarm Functions, Transformer Monitoring
RT-DUTY
Command
Purpose:
Read/Set Transformer Through Fault Duty Log
Syntax:
RT-DUTY[{n}{phase}[={%duty}]] where n=1,2,3,4 and %duty is % of dmax set with ST-
DUTY
Example:
RT-DUTY1A or RT-DUTY1B=50
Reference:
Section
6,
Reporting and Alarm Functions, Transformer Monitoring
RT-TFCNTR
Command
Purpose:
Read/Set Transformer Through Fault Counter
Syntax:
RT-TFCNTR[={#operations}]
Example:
RT-TFCNTR=32 or RT-TFCNTR=652
Reference:
Section
6,
Reporting and Alarm Functions, Transformer Monitoring
Setting Command
S
Command
Purpose:
Read all relay setting parameters
Syntax:
S
Example:
S
Reference:
Section
11,
ASCII Command Interface, Settings (S) Command Descriptions
Alarm Setting Commands
SA
Command
Purpose:
Read all alarm settings for Major, Minor and Logic alarms
Syntax:
SA
Example:
SA
Reference:
Section
6,
Reporting and Alarm Functions, Alarms Function
SA-24
Command
Purpose:
Read/Set Volts Per Hertz alarm settings
Syntax:
SA-24[={alarm level},{td(m)}] alarm level=volts per hertz
Example:
SA-24 or SA-24=1.1,2000 or SA-24=1.08,500
Reference:
Section
4,
Protection and Control, Voltage Protection
SA-27
Command
Purpose:
Read/Set Under Voltage alarm settings
Syntax:
SA-27[={alarm level}] where alarm level = volts
Example:
SA-27 or SA-27=110 or SA-27=5
Reference:
Section
4,
Protection and Control, Voltage Protection
SA-59
Command
Purpose:
Read/Set Over Voltage alarm settings
Syntax:
SA-59[={alarm level}] where alarm level = volts
Example:
SA-59 or SA-59=125 or SA-59=5
Reference:
Section
4,
Protection and Control, Voltage Protection
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......