9365200990 Rev F
BE1-CDS240 ASCII Command Interface
11-27
SG-DST
Command
Purpose:
Read/Set Daylight Saving Time (DST) type
Syntax:
SG-DST[=1/2] where 1 means floating date, and 2 means fixed date
Example:
SG-DST, SG-DST=1, SG-DST=2
Reference:
Section 6,
Reporting and Alarms Function, Clock
SG-DSTSTART
Command
Purpose:
Read/Set settings for start of Daylight Saving Time
Syntax:
SG-DSTSTART[={Mo,D,H,M,O}] where Mo=Month, D=Day of week (or month), H=Hour,
M=Min, O=# of occurrence of 'D' in the month]
Example:
SG-DSTSTART, SG-DSTSTART=3,1,2,0,1 (For 2AM Mar 1) or SG-
DSTSTART=4,0,2,15,2 (For 2:15AM on 2nd Sunday in April)
Reference:
Section 6,
Reporting and Alarms Function, Clock
SG-DSTSTOP
Command
Purpose:
Read/Set settings for end of Daylight Saving Time
Syntax:
SG-DSTSTOP[={Mo,D,H,M,O}] where Mo=Month, D=Day of week (or month), H=Hour,
M=Min, O=# of occurrence of 'D' in the month]
Example:
SG-DSTSTOP, SG-DSTSTOP=11,21,3,15,1 (For 3:15AM Nov. 21) or SG-
DSTSTOP=11,2,23,20,1 (For 11:20AM on 1st Tue in Nov.)
Reference:
Section 6,
Reporting and Alarms Function, Clock
SG-FREQ
Command
Purpose:
Read/Enter power system Frequency
Syntax:
SG-FREQ[={freq(HZ)}]
Example:
SG-FREQ=60 or SG-FREQ=50
Reference:
Section
3,
Input and Output Functions, Power System Inputs
SG-HOLD
Command
Purpose:
Read/Program Output Hold operation
Syntax:
SG-HOLD[n][={1/0 hold ena}] where 1=TRUE, 0=FALSE
Example:
SG-HOLD or SG-HOLD1=1 or SG-HOLD2=0
Reference:
Section
3,
Input and Output Functions, Outputs
SG-ID
Command
Purpose:
Read/Set relay ID, station ID, UserID1 and UserID2 used in reports
Syntax:
SG-ID[={relayID},{StationID},{UserID1},{UserID2}]
Example:
SG-ID=448,SUBSTATION3 or SG-ID=GEN3,POWERPOINT_SUB,POWER,PLANT3
Reference:
Section
6,
Relay Identifier Information
SG-IN
Command
Purpose:
Read/Set Input recognition/debounce
Syntax:
SG-IN[#[={r(ms)},{db(ms)}]] where ms=4-255msec
Example:
SG-IN or SG-IN3 or SG-IN3=4,16
Reference:
Section
3,
Input And Output Functions, Contact Sensing Inputs
SG-LOG
Command
Purpose:
Read/Set load profile interval
Syntax:
SG-LOG[={interval}] where interval is between 1 and 60 minutes
Example:
SG-LOG or SG-LOG=15
Reference:
Section
6,
Reporting and Alarm Functions, Demand Functions
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......