Command
Purpose
SN-343=62_INI,INI,NORMAL
Name switch to make SER easier to read.
SL-62=3,343,0
Enables 62 1-shot, retriggerable mode, 343 initiate, no blocking.
S0-62=15s,20s
Sets 62 delay at 15 seconds, 62 dropout at 20 seconds.
EXIT
Exit.
Y Save
settings.
Step 2:
Send the commands in Table 13-103 to the relay. These commands supply the 62 Timer with
a momentary initiate input by pulsing the 343 Switch from a FALSE state to a TRUE state and
then back to a FALSE state. You may view the state changes of the 343 Switch at front panel
interface \CTRL\43\343, Screen 2.1.4.
NOTE
The 343 Switch action is performed three times in this test. To illustrate the
action of the timer mode, the second 343 Switch action should be executed as
quickly as possible (within the 15 second duration of the pickup time delay).
Perform the third 343 Switch action after at least 15 seconds (the pickup timer
setting) have elapsed but before the 20-second dropout time delay expires. This
will illustrate the action of the timer mode. The time delay settings may be
increased if difficulty is encountered with repeating the 343 Switch actions.
Table 13-103. x62 Mode 3 Timer Initiate Commands
Command
Purpose
A=
Gains write access.
CS-343=P
Selects 343 for pulse operation.
CO-343=P
Executes 343 for pulse operation.
CS-343=P
Selects 343 for pulse operation.
CO-343=P
Executes 343 for pulse operation.
Wait at least 15 seconds (but no longer than 35 seconds) to execute the next commands.
CS-343=P
Selects 343 Switch for pulse operation.
CO-343=P
Executes 343 Switch for pulse operation.
Step 3:
Use the RS-LGC command to obtain an SER report and verify that the following actions were
logged. These events are illustrated in the timing diagram of Figure 13-21.
After a 343 pulse action (FALSE-TRUE-FALSE) was logged, the 62 Timer output did not go
TRUE because of a second FALSE to TRUE initiate signal action.
Approximately 15 seconds after the second 343 FALSE to TRUE initiate signal, the 62 Timer
output went TRUE. The timer output went FALSE when the third FALSE to TRUE initiate
signal forced the 62 Timer (T1) to restart.
Fifteen seconds after the third 343 FALSE to TRUE initiate signal, the 62 Timer output went
TRUE again and then went FALSE after the duration timer (T2) expired 20 seconds later.
13-82
BE1-CDS240 Testing and Maintenance
9365200990 Rev F
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......