200 ms
200 ms
200 ms
T1
T2
T1
T1
T2
~~
343
162
INI
1
Normal
0
D2595-04.vsd
08-10-00
~ ~
~ ~
~ ~
Figure 13-21. x62 Mode 3 (One-Shot Retriggerable) Timing Example
Mode 4 - Oscillator
Because this operating mode is not intended for general use, no testing procedure is provided.
Information about Mode 4 is available in Section 4,
Protection and Control, General Purpose Logic
Timers.
Mode 5 – Integrating Timer
Step 1:
Prepare for Mode 5 logic timer verification testing by sending the commands in Table 13-104
to the relay.
Table 13-104. x62 Mode 5 Test Commands
Command
Purpose
A=
Gains write access.
SL-N=NONE
Zero out custom logic settings. Overwrite with logic = None settings.
Y
Confirm overwrite.
SL-N=T62
Sets T62 as custom logic name.
SL-43=2
Enables 43 Switch ON/OFF mode.
SN-43=62_INI,PU,DO
Name switch to make SER easier to read.
SL-62=5,43,0
Enables 62 integrating mode, 43 initiate, no blocking.
S0-62=15s,5s
Sets T1 at 15 seconds, T2 at 5 seconds.
EXIT
Exit.
Y Save
settings.
NOTE
The CS and CO commands of Table 13-100 are performed three times. Follow
the timing sequence to illustrate timer mode action. The time delay settings may
be increased if difficulty is encountered with repeating the 43 Switch actions.
Step 2:
Send the commands in Table 13-105 to the relay. These commands supply a block input to
the 62 Timer by changing the 43 Switch state to TRUE.
Table 13-105. x62 Mode 5 Timer Initiate Commands
Command
Purpose
A=
Gains write access.
CS-43=1
Selects 43 for TRUE operation.
CO-43=1
Executes 43 for TRUE operation.
Wait no longer than 10 seconds to interrupt the T1 Timer.
CS-43=0
Selects 43 for FALSE operation.
CO-43=0
Executes 43 for FALSE operation.
9365200990 Rev F
BE1-CDS240 Testing and Maintenance
13-83
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......