13-88
BE1-CDS240 Testing and Maintenance
9365200990 Rev F
Table 13-111. Automatic Setting Group Change Example Accuracy Limits - Increasing Current
Current Value
Sensing
Type
Above Switch
Threshold
But Below Next
Group Switch
Threshold and 51P
PU
Time Comments
0.51 A
0.73 A
-
Starting point 50% of S0-51P pickup
0.77 A
0.88 A
> 1 min
Switch to SG1 (75% S0 51P pickup)
0.92 A
1.07 A
> 1 min
Switch to SG2 (90% S0 51P pickup)
1 A
1.13 A
2.1 A
> 1 min
Switch to SG3 (110% S0 51P pickup)
2.55 A
3.6 A
-
Starting point 50% pickup
3.83 A
4.4 A
> 1 min
Switch to SG1 (75% S0 51P pickup)
4.59 A
4.595 A
> 1 min
Switch to SG2 (90% S0 51P pickup)
5 A
5.61 A
10.78 A
> 1 min
Switch to SG3 (110% S0 51P pickup)
Step 6:
Verify that SG3 is the active setting group by sending the command RG-GRPACTIVE to the
relay. It should echo back that the SG3 is the active group. With the HMI, you may also verify
the active setting group at the front panel interface Screen \STAT\OPER\ACTIVEG, 1.4.4.
Step 7: Send to the relay the commands in Table 13-112.
Table 13-112. Automatic Group Control Selection
Command Purpose
A= Gain
access.
CS-143=1
Selects 143 for TRUE operation.
CO-143=1
Executes 143 TRUE operation (Setting Group 1).
E Exit.
Step 8:
Verify that the relay did not change to Setting Group 1 (SG1) by transmitting the RG-
GRPACTIVE to the relay. It should echo back that the SG3 is still the active group. This
verifies that the relay will not make any setting group changes from logic inputs while the
AUTO input logic is TRUE.
Step 9:
Begin stepping down the level of current from one level to the next as shown in Table 13-113.
First step the current to just below the threshold limit for the amount of time listed. Monitor the
output contacts to verify that the setting group changed. If the active setting group does not
change, step the current down to just above the next group switch limit for the duration
indicated. This will verify the accuracy of the pickup return threshold. Continue stepping down
to each new level.
Table 13-113. Automatic Setting Group Change Example Accuracy Limits - Decreasing Current
Current Value
Sensing
Type
Below Switch
Timing
Threshold
But Above Next
Group Switch
Threshold
Time Comments
2.1 A
1.13 A
> 1 min SG3 (110% SG0 51P).
0.98 A
0.86 A
> 1 min Switch to SG2 (100% SG0 51P).
0.83 A
0.71 A
> 1 min Switch to SG1 (85% S0 51P pickup).
1 A
1.13
2.1
> 1 min Switch to SG0 (70% S0 51P pickup).
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......