Table 4-26 summarizes the BESTlogic settings for Negative-Sequence Overvoltage.
Table 4-26. BESTlogic Settings for Negative-Sequence Overvoltage
Function Range/Purpose Default
Mode
0 = Disabled
1 = Enabled
1
BLK
Logic expression that disables function when TRUE. A
setting of 0 disables blocking.
0
Example 1.
Make the following BESTlogic settings to the 47 element. Refer to Figure 4-44.
Mode:
Enable
BLK:
0
Operating Settings for Negative-Sequence Overvoltage
Operating settings are made using BESTCOMS. Figure 4-45 illustrates the BESTCOMS screen used to
select operational settings for the negative-sequence overvoltage element. To open the screen select
Voltage Protection
from the
Screens
pull-down menu and then select the
47
tab. Alternately, settings
maybe made using the S<g>-47 ASCII command or through the optional HMI interface using Screen
5.#.7.1, \PROT\SG#\47\47.
Figure 4-45. Voltage Protection Screen, 47 Tab
Beside the
Logic
pull-down menu is a pull-down menu labeled
Settings
. The Settings menu is used to
select the setting group that the elements settings apply to.
The default unit of measure for the
Pickup
setting is secondary volts. Primary volts (Pri Volts), per unit
volts (Per U Volts), and percent volts (% Volts) can also be selected as the pickup setting unit of
measure. The unit of measure for the
Time
setting that represents the element's time delay defaults to
milliseconds. It is also selectable for seconds, minutes, and cycles.
4-50
BE1-CDS240 Protection and Control
9365200990 Rev F
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......