Over/Underfrequency function by selecting its mode of operation from the
Mode
pull-down menu. To
connect the elements inputs, select the button for the corresponding input in the
BESTlogic Function
Element
screen. The
BESTlogic Expression Builder
screen will open. Select the expression type to be
used. Then, select the BESTlogic variable, or series of variables to be connected to the input. Select
Save
when finished to return to the
BESTlogic Function Element
screen. For more details on the
BESTlogic Expression Builder
, see Section 7,
BESTlogic Programmable Logic
. Select
Done
when the
settings have been completely edited.
BESTlogic settings for Over/Underfrequency are summarized in Table 4-28.
Table 4-28. BESTlogic Settings for Over/Underfrequency
Function Range/Purpose
Default
Mode
0 = Disabled
1 = Enabled on VP input
0
BLK
Logic expression that disables function when TRUE.
0
Example 1.
Make the following BESTlogic settings to the 81 element. Refer to Figure 4-47.
Mode:
Phase VT Input
BLK:
0
Operating Settings for Over/Underfrequency
Operating settings for the 81 elements consist of pickup values, time delay values, and a mode setting
that defines whether an element provides under or over frequency protection and is selectable from a
pull-down menu under each element tab. The pickup value determines the value of frequency required for
the element to start timing toward a trip. The time delay value determines the length of time between
reaching the pickup value and tripping. Time delays can be set in milliseconds, seconds, or cycles. The
default is milliseconds if no unit of measure is specified. Minimum timing resolution is two cycles. A time
delay setting of zero makes the element instantaneous with no intentional time delay.
Operating settings are made using BESTCOMS. Figure 4-48 illustrates the BESTCOMS screen used to
select operational settings for the Over/Underfrequency element. To open the
BESTlogic Function
Element
screen for Over/Underfrequency element, select
Voltage Protection
from the
Screens
pull-down
menu and select the
INH/81/181/281/381/481/581
tab. Alternately, settings may be made using the S<g>-
<x>81 ASCII command or the optional HMI interface using Screens 5.#.10.1 and 5.#.10.2,
\PROT\SG#\81\SETTINGS.
Figure 4-48. Voltage Protection Screen, INH/81/181/281/381/481/581 Tab
9365200990 Rev F
BE1-CDS240 Protection and Control
4-53
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......