TRANSFORMER MONITORING FUNCTIONS
The transformer monitoring functions provide monitoring and alarms for the transformer to help manage
equipment inspection and maintenance expenses. Transformer monitoring functions include through-fault
counter reporting and through-fault current duty monitoring. Each of these functions can be set as a
programmable alarm. See the paragraphs on
Alarms Function,
later in this section for more information
on the use of programmable alarms.
Number of Through Faults Monitoring Function
This function monitors the SG-TRIGGER pickup logic expression. It increments the count in the
operations counter register each time that the SG-TRIGGER pickup logic expression is true and returns to
false. For more information on this function and the SG-TRIGGER pickup expression, see the illustration
and paragraphs later in this section on
Fault Reporting.
Retrieving Through Fault Operation Counter Information
The current value of the through-fault operations counter register can be read from HMI Screen 4.5.1,
\REPRT\XFORM\STATUS. Pressing the
Edit
key allows the user to enter a number into the register to
preset it to a value if desired. Write access to the reports functional area must be gained to edit this value
at the HMI. The current value of the breaker operations counter can also be read or preset from the ASCII
command interface using the RT-TFCNTR (report transformer, through-fault counter) command.
The through fault counter can be monitored to give an alarm when the value exceeds a threshold. See
Transformer Alarms
in this section for more information on this feature.
Transformer Duty Monitoring
The transformer duty monitoring function accumulates the maximum current in each phase of the
transformer when a through fault occurs. A through fault is defined as whenever the pickup expression
set with the SG-TRIGGER command is true.
Every time the pickup expression in the SG-TRIGGER command is true, the transformer duty monitoring
function updates two sets of registers for each phase of the transformer. (Only the CT selected by the
transformer duty monitoring function (ST-DUTY) is monitored.) In the accumulated
I*t
Duty registers,
the function adds the maximum measured current in primary-ampere seconds. In the accumulated
I2*t
Duty registers, the function adds the maximum measured current squared in primary-ampere seconds.
The
t
is calculated from the time the pickup expression is TRUE. The user selects which of the six sets of
duty registers are reported and monitored by the function when setting up the mode setting in ST-DUTY.
The value in each set of duty registers is calculated and stored in primary ampere seconds or primary-
amperes squared seconds as appropriate. This value is reported, however, as a percent of maximum.
The user sets the value that the relay will use for 100% duty (DMAX). The value set for maximum duty is
used directly for reporting the accumulated
I*t
Duty registers or
I2*t
Duty registers.
When testing the relay by injecting currents into the relay, the values in the duty registers should be read
and recorded prior to the start of testing. Once testing is complete and the relay is returned to service, the
registers should be reset to the original pre-test values. A block accumulation logic input may be used
when testing so that simulated transformer duty is not added to the duty registers. The BLKTXFMR logic
function is an OR logic term (e.g., IN1 or VO7) which blocks the transformer monitoring logic when TRUE
(1). BLKTXFMR may be set to zero to disable blocking. When transformer monitoring is blocked (logic
expression is equal to 1), transformer through faults are not counted or accumulated. It should be noted
that even though a BESTlogic logic expression is used to make this setting, this setting is not included in
the section on BESTlogic settings.
Setting the Transformer Duty Monitoring Function
The transformer monitoring function can be set from BESTCOMS (Figure 6-7). Pull down the
Screens
menu and select
Reporting and Alarms.
Select the
Transformer Monitoring
tab. Alternately, settings can
be made using the ASCII command ST-DUTY (setting transformer, duty) command or the HMI using
Screen 6.6.1, \SETUP\XFRMR\DUTY. This function selects the transformer CT to be monitored that also
affects the transformer alarm function (SA-TX). Table 6-8 lists the settings for the transformer duty
monitoring function.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......