8-52
BE1-CDS240 Application
9365200990 Rev F
State Labels
Output Purpose
Description
Label
True False
VO15 Unbalance
alarm.
TRUE if unbalance (51Q) protection
is picked up. This condition will trip
the motor if allowed to time out.
UNBALANCE ALARM NORMAL
BESTlogic Expression: VO15=51QPU
Table 8-36. CDS240-MOTR-A-BE Hardware Output Logic
Output Purpose
Description
OUTA
Relay Trouble Alarm.
OUTA contact closes when relay trouble alarm occurs.
BESTlogic Expression: OUTA=VOA
OUT1
Breaker trip.
OUT1 contact closes when protective trip expression is TRUE.
BESTlogic Expression: OUT1=VO1
OUT4
Overload alarm output
contact.
OUT4 contact closes when Overload protection (51P) is picked up and
timing to trip.
BESTlogic Expression: OUT4=VO4
OUT5
Unbalance alarm output
contact.
OUT5 contact closes when Unbalance protection (51Q) is picked up
and timing to trip.
BESTlogic Expression: OUT5=VO5
OUT7 -
14
Spare output contacts.
N/A
BESTlogic Expression: OUT7-14 =0
MISCELLANEOUS LOGIC EXPRESSIONS
Several logic expressions are classified as miscellaneous. That is, they are not included in the BESTlogic
settings and are not set through the ASCII command interface using the SL (set logic) commands.
Several of the Reporting And Alarm Functions provided in the relay require programmable logic
expressions to determine their functionality. These logic expressions are included with the settings
associated with each function. Table 8-37 cross-references the manual Sections and commands
associated with each miscellaneous logic expression.
Each of the preprogrammed logic schemes is designed to be compatible with the factory default logic
expression settings for these Reporting And Alarm Functions. However, when copying a preprogrammed
scheme for modification or direct use, it is important to recognize that these miscellaneous logic
expressions will not be effected. These miscellaneous logic settings must be reviewed to ensure desired
performance for these functions.
Table 8-37. Miscellaneous Logic Expressions
Command Reference
SA-RESET Section
6,
Reporting and Alarm Functions, Alarms Function
SB-DUTY Section
6,
Reporting and Alarm Functions, Breaker Monitoring
SB-LOGIC Section
6,
Reporting and Alarm Functions, Breaker Monitoring
SG-TARG Section
6,
Reporting and Alarm Functions, Fault Reporting
SG-TRIGGER Section
6,
Reporting and Alarm Functions, Fault Reporting
ST-DUTY Section
6,
Reporting and Alarm Functions, Transformer Monitoring
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......