9365200990 Rev F
BE1-CDS240 ASCII Command Interface
11-3
Example 2.
Read all peak-since-reset demand current registers. Entering RD2-PI (Report Demand -
Peak Current (I)) will return demand values and time stamps for phase A, B, C, neutral,
and negative sequence current for current input circuit 2. To read only the neutral
demand value, the full object name (RD2-PIN) is entered. Entering RD2-PI=0 resets all
five of the peak-since-reset current demand registers.
Command Text File Operations
In command text file operations, an ASCII text file of commands is created and sent to the relay. For
example, the S command is used to retrieve a complete list of settings from the relay in ASCII command
format. This list of commands is captured, saved to a file, edited with any ASCII text editor, and then
uploaded to the relay. Because the number of relay settings is so large, loading settings with a text file is
the preferred method of setting the BE1-CDS240.
Embedding Comments into ASCII Text Files
Adding comments to ASCII settings files is an easy way to organize and label your settings. A comment
line is started with two forward slashes (//) followed by the comment text. When the relay encounters // in
a text file, it ignores all following characters until the next carriage return or linefeed character.
Example of embedding comments in a settings file:
//Group0 is used during normal operation
>S0-50TP=7.50,0m;S0-50TN=2.5,0m . . .
//Group1 is used during cold load pickup
>S1-50TP=0,0m; S1-50TN=0,0m; S1-50TQ=0,0m
Miscellaneous Command Descriptions
HELP Command
The HELP (H) command provides general information on command syntax and functionality when the
manual is not available. Entering HELP or H provides information about using the HELP command.
HELP1 or H1 returns a complete list of relay commands. Entering HELP <cmd> where <cmd> is a
specific command, returns information about the use and format of the command along with an example
of how the command is used.
HELP
Command
Purpose:
Obtain help on command operation
Syntax:
HELP {cmd} or H {cmd} for help on {cmd}, H1 for command list
Example:
HELP, H1, H SG-COM
ACCESS Command
Before making settings changes through a communication port, the ACCESS command must be used to
obtain programming access. Enter ACCESS=<password> to obtain access to change settings associated
with the password. Different passwords give the ability or access to perform different operations. The
relay will deny access if an invalid password is entered or if another user has already been granted
programming access through another serial port or at the front panel. Only one user can have access at
any one time.
Even if password protection is not used, it is still necessary to obtain access so that accidental changes
are prevented. If password protection is disabled, then ACCESS= will be accepted in place of a
password. The relay will respond with
ACCESS GRANTED: GLOBAL
if the command entered was
received and executed. The relay will respond with an error message and a ‘?’ if the command could not
be executed.
The ACCESS (A) command and the EXIT (E) command are used to change relay settings, reset report
registers, and enable control commands through a serial port. These commands prevent changes from
being made concurrently from two areas. For example, a user cannot make changes through COM 0 at
the same time a remote user is making changes through COM 2.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......