11-4
BE1-CDS240 ASCII Command Interface
9365200990 Rev F
ACCESS
Command
Purpose:
Read/Set Access level in order to change settings
Syntax:
ACCESS[={password}]
Example:
ACCESS=CDS
Comments:
The ACCESS command must be used before any changes to settings can be made.
Available ACCESS privileges are summarized in the following paragraphs.
READ-ONLY: This is the default access privilege when no passwords are active. Read-only access
allows you to read settings and reports but not make settings changes.
PRIVILEGE G: GLOBAL ACCESS. Global access is obtained by password G (PWG). Global access
permits entry of any command with no restrictions.
PRIVILEGE S: SETTING ACCESS. Setting access is obtained by password S (PWS). Setting access
allows changes to any settings.
PRIVILEGE C: CONTROL ACCESS. Control access is obtained by password C (PWC). Control access
enables relay control operations.
PRIVILEGE R: REPORT ACCESS. Report access is obtained by password R (PWR). Report access
enables report operations to be performed.
An access privilege is obtained only when the appropriate password is entered. When a valid password is
entered, the relay responds with the access privilege provided by the password entered. If an invalid
password is entered, an error message is returned. If password protection is disabled in one or more
privileges, then entering any string will provide access to the unprotected privileges.
Note:
In examples throughout this manual, relay responses are printed in
Courier New
typeface.
ACCESS Command Examples:
Example 1.
A valid password is entered.
>ACCESS=OPENUP
ACCESS GRANTED: GLOBAL
Example 2.
An invalid password is entered.
>ACCESS=POENUP
ACCESS DENIED
Example 3.
The current access privilege is read.
>ACCESS
ACCESS: GLOBAL
EXIT Command
After changes are made, the new data is saved or discarded using the EXIT command. Prior to saving or
discarding any changes, you must confirm that you wish to exit the programming mode. There is three
exit options: Y (yes), N (no), or C (continue).
EXIT
Command
Purpose:
Exit programming mode
Syntax:
EXIT (Note: Relay will prompt for verification.)
Example:
EXIT
Comments:
It's important to make all programming changes before executing the EXIT command.
This prevents a partial or incomplete protection scheme from being implemented.
When access privileges are obtained, all programming changes are made to a temporary, scratchpad
copy of relay settings. These changes aren't saved to nonvolatile memory and initiated until the EXIT
command is invoked and confirmed. After the EXIT command is entered, the relay prompts to confirm that
the new data should be saved. Three options, Y, N, or C are available. Entering Y will save the data. If N
is entered, the relay will clear the changes and resume operating with the old settings. Entering C will
abort the EXIT command and allow programming to continue.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......