NOTE
In verifying output connections, we pulse the hardware outputs for 200
milliseconds. If you have a specific output that requires a longer operate time to
verify operation, substitute a 1 or 0 (depending on the output logic) for the P in
the commands listed in Table 13-17. After the output connection is verified, it is
important to return the output to logic control using the commands CS-OUTn=L;
CO-OUTn=L <enter>.
If desired, you may disable the control override capability by transmitting the
commands ACCESS=, CS-OUT=DIS, CO-OUT=DIS, EXIT and YES to the relay.
Table 13-17. Output Control Override Commands
Output Terminals
Commands
ALARM (N.C.)
C1 and C2
CS-OUTA=P,CO-OUTA=P
OUT1 (NC/NO)
C3, C4 and C5
CS-OUT1=P,CO-OUT1=P
OUT2 (NC/NO)
C6, C7 and C8
CS-OUT2=P,CO-OUT2=P
OUT3 (N.O.)
C9 and C10
CS-OUT3=P,CO-OUT3=P
OUT4 (N.O.)
C11 and C12
CS-OUT4=P,CO-OUT4=P
OUT5 (N.O.)
C13 and C14
CS-OUT5=P,CO-OUT5=P
OUT6 (N.O.)
C15 and C16
CS-OUT6=P,CO-OUT6=P
OUT7 (N.O.)
C18 and C19
CS-OUT7=P,CO-OUT7=P
OUT8 (N.O.)
C20 and C21
CS-OUT8=P,CO-OUT8=P
OUT9 (N.O.)
C22 and C23
CS-OUT9=P,CO-OUT9=P
OUT10 (N.O.)
C24 and C25
CS-OUT10=P,CO-OUT10=P
OUT11 (N.O.)
C26 and C27
CS-OUT11=P,CO-OUT11=P
OUT12 (N.O.)
C28 and C29
CS-OUT12=P,CO-OUT12=P
OUT13 (N.O.)
C30 and C31
CS-OUT13=P,CO-OUT13=P
OUT14 (N.O.)
C32 and C33
CS-OUT14=P,CO-OUT14=P
Virtual 43 Switches
Purpose:
To verify the operation, labels and logic settings of the virtual 43 switches.
Reference Commands:
SN-43, SL-43, RG-43STAT, RG-STAT, CS/CO-43
NOTE
If virtual 43 switches are not used, skip the eight associated steps and go to the
next test.
Step 1:
Transmit the SN-43 command to verify the Virtual Selector Switch 43 name, TRUE label, and
FALSE label. This information is reported using the format SN-x43=name, TRUE label, FALSE
label.
Step 2:
Repeat Step 1 for Virtual Selector Switches 143 through 743. Use the number of a switch in
the SN-43 command to retrieve name and label information for that switch.
Step 3:
Use the SL-x43 command to obtain the logic setting of Virtual Switches 43 through 743. Logic
settings for virtual switches can also be obtained by using the SL command. Verify that the
desired virtual selector switch setting matches the reported setting.
9365200990 Rev F
BE1-CDS240 Testing and Maintenance
13-23
Step 4:
Transmit the RG-43STAT command to obtain the position of the eight virtual selector
switches. Alternately, the virtual selector switch positions can be obtained through the RG-
STAT command or HMI Screens 2.1.1 through 2.1.8, \CTRL\43\43 through \CTRL\43\743.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......