Command Purpose
S#-87=0.35,15,18,0,0,1
Minpu = 0.35, slope = 15% ,2
nd
= 18%, 5
th
= disabled, URO =
disabled, 2
nd
harmonic sharing = shared.
E Exit.
Y Save
settings.
Step 3:
Apply 2.0 amps of 60 Hz current to the A-phase Input 1. The OUT1 (87RT restrained trip)
output contact should close upon application of current.
Step 4:
Apply 120 Hz current on the source paralleled to A-phase Input 1 and slowly increase the
current from zero until OUT2 closes (and conversely, OUT1 opens).
Step 5:
Record the current magnitude from Step 4 that caused OUT 2 to close and OUT1 to open.
These output contact changes indicated that the 2
nd
harmonic restraint function is now
restraining the 87RT operation.
Step 6:
Remove both 60 Hz and 120 Hz currents.
Step 7:
To arrive at a 2
nd
harmonic inhibit percentage value, divide the magnitude of the applied 2
nd
harmonic current (120 Hz) by the magnitude of the applied 60 Hz input current. For this
particular test, this value should be equal to 0.36 amperes @ 120 Hz 2 A @ 60 Hz = 18 %.
Verify that the 2
nd
harmonic inhibit function restrains operation at the expected value based on
settings from Step 2. The recommended CT connection for this test is WYE. If the user
decides to use a DELTA CT connection, the 2
nd
harmonic current will be doubled as a result of
delta summation and the relay will operate at 9%.
Step 8:
(Optional.) Repeat Steps 2 through 7 for phases B and C. Because the relay was set for
harmonic sharing in the S#-87 command (the last “1” in the string) in Step 2, the harmonic
content on all phases is shared or summed. This magnitude is used by the second harmonic
comparators for each phase. Thus, the same operation will occur regardless of which phase of
the 120-hertz test current is applied.
Step 9:
(Optional.) Repeat Steps 2 through 8 for Setting Groups 1 through 3 using the CS/CO-
GROUP command to change setting groups.
Step 10: (Optional.) Repeat for each pair of CT inputs (CT1-CT3, CT1-CT4, CT2-CT3, CT2-CT4, and
CT3-CT4).
Fifth Harmonic Restraint Verification
Purpose:
To verify the operation of the 5
th
harmonic restraint function of the 87 element.
Reference Commands:
SL-87, S(n)-87, S(n)-TAP87, SL-VO, SG-CT.
Step 1:
Parallel a 60 Hz current source and a second 300 Hz current source to Terminals A3, A4
(A-phase, Input 1). Same as Figure 13-14 except for the applied harmonic frequency.
An ohmmeter or continuity tester may be used to monitor output contact status.
Step 2:
Send the commands listed in Table 13-35 to the relay to setup a test of the pickup of the fifth
harmonic restraint elements.
Table 13-35. Fifth Harmonic Restraint Elements Setup Commands
Command Purpose
A= Gain
access.
SL-N=NONE
Zero out custom logic settings/overwrite with logic = None settings.
Y Confirm
overwrite.
SL-N=5HAR
Sets 5HAR as custom logic name.
SL-87=1,0 Enables
87.
SL-VO1=87RT
Enables OUT1 to close with 87 restrained trip.
SL-VO2=5THHAR
Enables OUT2 to close when 5
th
harmonic restrains 87RT.
SG-CT1=1,WYE,NA,0
Ctr = 1, ct = wye, xfmr = na, no ground source.
9365200990 Rev F
BE1-CDS240 Testing and Maintenance
13-49
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......