13-68
BE1-CDS240 Testing and Maintenance
9365200990 Rev F
Step 5:
Slowly decrease the A-phase voltage until OUT1 closes. Pickup should occur 2
percent or 1 volt of the 27 pickup setting. Slowly increase the A-phase voltage until OUT1
opens. Dropout should occur between 102 and 103 percent of the actual pickup value. Verify
the 27A target and the HMI. Reset the target.
Step 6:
Continue increasing the A-phase voltage until OUT1 closes. Pickup should occur 2
percent or 1 volt of the 59 pickup setting. Slowly reduce the A-phase voltage until OUT1
opens. Dropout should occur between 97 and 98 percent of the actual pickup value. Verify
59A target on the HMI.
Step 7:
Verify the pickup and dropout accuracy of the middle and upper pickup settings listed in Table
13-68.
Step 8:
(Optional.) Repeat Steps 2 through 7 for the B-phase and C-phase voltage inputs.
Step 9:
(Optional.) Repeat Steps 2 through 8 for Setting Groups 1, 2, and 3.
Step 10: (Optional.) Repeat Steps 2 through 7 for 127 and 159 elements).
Phase Undervoltage and Overvoltage Timing Verification
Step 1:
Using Table 13-69 as a guide, transmit the first row of setting commands to the relay.
Table 13-69. 27, 59 Pickup and Time Delay Settings
Pickup and Time Delay Settings
Undervoltage
Overvoltage
Purpose
S0-27=72,2s S0-59=156,2s
Sets 27 PU at 72 V, 59 at 156 V
Sets 27 TD, 59P TD at 2 seconds
S0-27=,5s S0-59=,5s Sets
27
TD, 59P TD at 5 seconds
S0-27=,10s S0-59=,10s Sets
27 TD, 59P TD at 10 seconds
Step 2:
Prepare to monitor the 27 and 59 timings. Timing accuracy is verified by measuring the
elapsed time between a sensing voltage change and OUT1 closing.
Step 3:
Connect and apply a 120 Vac, three-phase voltage source to terminals B9 (A-phase), B10
(B-phase), B11 (C-phase), and B12 (Neutral). Refer to Figure 13-1 for terminal locations.
Step 4:
Step the A-phase voltage down to 68 volts. Measure the time delay and verify the accuracy of
the 27 time delay setting. Timing accuracy is +5 percent or +3 cycles of the time delay setting.
Step 5:
Step the A-phase voltage up to 165 volts. Measure the time delay and verify the accuracy of
the 59 time delay setting. Timing accuracy is +5 percent or +3 cycles of the time delay setting.
Step 6:
Repeat Steps 5 and 6 for the middle and upper time delay settings of Table 13-69.
Step 7:
(Optional.) Repeat Steps 2 through 6 for the B-phase and C-phase voltage inputs.
Step 8:
(Optional.) Repeat Steps 2 through 7 for Setting Groups 1, 2, and 3.
Step 9:
(Optional.) Repeat Steps 2 through 7 for 127 and 159 elements.
Negative-Sequence Voltage (47)
Negative-Sequence Voltage Pickup Verification
Step 1:
Prepare the 47 pickup function for testing by transmitting the commands in Table 13-70 to the
relay. Reset targets.
Table 13-70. 47 Pickup Test Commands
Command
Purpose
A=
Gains write access.
SL-N=NONE
Zero out custom logic settings.
Overwrite with logic = None settings.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......