BE1-CDS240 Testing and Maintenance
13-79
Table 13-95. 101 Virtual Breaker Control Switch Trip Test Commands
Command
Purpose
A=
Gains write access.
CS-x101T=T
Selects x101T for trip operation.
CO-x101T=T
Executes x101T for trip operation.
Step 8:
Send the commands in Table 13-96 to the relay or, navigate to Screen \CTRL\BKR to set the
mode of the x101 Virtual Breaker Control Switch to the close state.
Result:
OUT2 contact closes for 200 milliseconds and returns to the open state and OUT3 contact
closes (close state) and remains closed.
Table 13-96. x101 Virtual Breaker Control Switch Close Test Commands
Command
Purpose
A=
Gains write access.
CS-x101C=C
Selects x101C for close operation.
CO-x101C=C
Executes x101C for close operation.
Step 9:
Repeat for each of the x101 switches.
Logic Timer Verification (62/162/262/362)
Mode 1 - Pickup/Dropout
Purpose
: To verify the operation of the 62 timer elements.
Reference Commands
: SL-62/162/262/362, S<g>-62/162/262/362
Step 1:
Prepare for Mode 1 logic timer verification testing by sending the commands in Table 13-97 to
the relay.
Table 13-97. x62 Mode 1 Test Commands
Command
Purpose
A=
Gains write access.
SL-N=NONE
Zero out custom logic settings. Overwrite with logic = None settings.
Y
Confirm overwrite.
SL-N=T62
Sets T62 as custom logic name.
SL-43=2
Enables 43 Switch ON/OFF mode.
SN-43=62_INITIATE,PU,DO
Name switch to make SER easier to read.
SL-62=1,43
Enables 62 PU/DO mode, 43 initiate, no block.
S# -62=400m,2000m
Sets 62 pickup = 400 ms, dropout = 2,000 ms
EXIT
Exit.
Y Save
settings.
Step 2:
Send the commands in Table 13-98 to the relay. These commands will initiate the 62 Timer by
changing the 43 Switch state to closed (logic 1). Once initiated, the 62 Timer will force an
output based on the 400-millisecond pickup time setting.
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......