NOTE
The CT input circuit settings are used by the auto-tap calculation function to
calculate the correct tap adjustment factor for the differential functions. When
entering these settings via the ASCII command interface, the validation routine
and auto-tap calculation is performed on exit after all parameters have been
entered.
When entering these settings using the optional HMI, the validation routine and
auto-tap calculation is performed on exit of each screen. This may cause an
OUT
OF RANGE
error message from the auto-tap calculation function. The user is
advised to enter valid CT input circuit settings on Screen 6.3.1.1,
SETUP\PWR_S\CON\CTP prior to entering the auto-tap calculation settings. If
the user has previously set the auto-tap calculation settings and needs to change
the CT input circuit settings, it may be necessary to temporarily change the auto-
tap function setting to
MANUAL
on Screens 5.1.1.3, 5.2.1.3, 5.3.1.3, and 5.4.1.3
\PROT\SG#\87\TAP in order to enter the new CT settings.
See Section 3,
Input and Output Functions, Power System Inputs,
for more
information on CT input circuit settings.
The tap factors calculated by the auto-tap calculation feature can be determined in several ways. They
are displayed on the optional HMI using Screen 5.#.1.2, \PROT\SG#\87\MVA. Alternatively, the current
check record provided by the differential alarm function includes a listing of the compensation parameters
in the setting group that was active at the time that the record was triggered. See Section 6,
Reporting
and Alarm Functions, Differential Current Monitoring Function, Setting Differential Current Monitoring
Alarms,
for more details on this report.
Operating Settings for Phase Differential
Operating settings for the 87 function consist of
Restrained Pickup
,
Restraint Slope
,
2
nd
and 5
th
Harmonic
Restraint
, and
Unrestrained Pickup
values.
Operating settings are made using BESTCOMS. Figure 4-12 illustrates the BESTCOMS screen used to
select operational settings for the 87 function. To open the screen, select
Percentage Differential
from the
Screens
pull-down menu. Then select the
87 Phase
tab. Alternately, settings may be made using S<g>-
87 ASCII command or through the optional HMI Screens 5.#.1.1, \PROT\SG#\87\87.
The operating settings for Phase Differential are provided in Table 4-7.
The settings for restrained minimum pickup and unrestrained trip are set in multiples of tap. If the ideal
taps calculated by Equation 4-1 fell within the acceptable range, the sensitivity settings will be in
Per Unit
on the MVA Base used in the equation. For example, a 100 MVA, 115 KV transformer has a full load (1
per unit) current of 500 amperes. A pickup setting of 10 times tap for the unrestrained output pickup
(URO) element is equivalent to 5,000 primary amperes of differential current.
If the taps had to be adjusted upwards or downwards to fit within the acceptable range, the sensitivity
settings for these protective elements should be adjusted as well. Equation 4-2 gives the adjustment
factor. The definitions for the variables in Equation 4-2 are the same as those for Equation 4-1. For
example, the ideal taps
(
TAPn
I
)
were calculated using Equations 4-2 and 4-3 to be 1.6 and 5.0. They had
to be adjusted upwards so that the actual taps
(
TAPn
A
)
are 2.0 and 6.25. Per Equation 4-2,
X
is 0.8. It is
desired that the minimum pickup of the restrained element be 0.35 per unit on the circuit base. The actual
setting should be 0.35
0.8 = 0.28 to achieve the same sensitivity.
The pickup settings in
Times Tap
can be related to primary amps by Equation 4-3.
Minpu
is the minimum
pickup setting in Times Tap. The definitions for the remaining variables in Equation 4-3 are the same as
those for Equation 4-1.
CTRn
*
KVn
*
3
*
TAPn
COMPn
*
1000
*
MVA
TAPn
TAPn
X
A
A
I
Equation 4-2. Tab Adjustment Equation
COMPn
CTRn
*
TAPn
*
Mpu
Ipri
Equation 4-3. Calculate Primary Amps
9365200990 Rev F
BE1-CDS240 Protection and Control
4-15
Summary of Contents for BE1-CDS240
Page 2: ......
Page 8: ...vi BE1 CDS240 Introduction 9365200990 Rev F This page intentionally left blank ...
Page 38: ...1 28 BE1 CDS240 General Information 9365200990 Rev F This page intentionally left blank ...
Page 40: ...ii BE1 CDS240 Quick Start 9365200990 Rev F This page intentionally left blank ...
Page 152: ...ii BE1 CDS240 Metering 9365200990 Rev F This page intentionally left blank ...
Page 226: ...iv BE1 CDS240 Application 9365200990 Rev F This page intentionally left blank ...
Page 286: ...ii BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 290: ...9 4 BE1 CDS240 Security 9365200990 Rev F This page intentionally left blank ...
Page 292: ...ii BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 306: ...10 14 BE1 CDS240 Human Machine Interface 9365200990 Rev F This page intentionally left blank ...
Page 308: ...ii BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 342: ...11 34 BE1 CDS240 ASCII Command Interface 9365200990 Rev F This page intentionally left blank ...
Page 349: ...Figure 12 5 Horizontal Rack Mount Front View 9365200990 Rev F BE1 CDS240 Installation 12 5 ...
Page 361: ...Figure 12 17 Typical DC Connection Diagrams 9365200990 Rev F BE1 CDS240 Installation 12 17 ...
Page 372: ...12 28 BE1 CDS240 Installation 9365200990 Rev F This page intentionally left blank ...
Page 468: ...13 92 BE1 CDS240 Testing and Maintenance 9365200990 Rev F This page intentionally left blank ...
Page 512: ...14 42 BE1 CDS240 BESTCOMS Software 9365200990 Rev F This page intentionally left blank ...
Page 544: ...ii BE1 CDS240 Terminal Communication 9365200990 Rev F This page intentionally left blank ...
Page 550: ...ii BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 578: ...D 28 BE1 CDS240 Settings Calculations 9365200990 Rev F This page intentionally left blank ...
Page 579: ......