BE1-DFPR Testing
5-21
30 milliseconds, whichever is greater, of the desired 79 4 TD setting in the Relay Settings screen.
Reset Timer
Step 45. Close the RI switch on the test set. Connect a voltage source to the voltage inputs and apply a
voltage that is greater than the 27 PU setting in the Relay Settings screen.
Step 46. Close the breaker on the test set and wait for the RST LED to illuminate on the relay.
Step 47. Initiate a Reclosing sequence. Measure the time from when the test set breaker closes until the
relay BLTC contacts close. This time should be within 5% of the desired 79 RESET setting in the
Relay Settings screen.
Reclose Fail Timer
Step 48. Close the RI switch and disable the Close 1 signal on the test set. Connect a voltage source to
the voltage inputs and apply a voltage that is greater than the 27 PU setting in the Relay Settings
screen.
Step 49. Close the breaker on the test set and wait for the RST LED to illuminate on the relay.
Step 50. Initiate a Reclosing sequence. Measure the time that the Close 1 contacts are closed. This time
should be within 5% of the 79 RECF setting in the Relay Settings screen.
Step 51. Enable the Close 1 signal on the test set.
Max Cycle Timer
Step 52. Close the RI switch on the test set. Connect a voltage source to the voltage inputs and apply a
voltage that is greater than the 27 PU setting in the Relay Settings screen.
Step 53. In the Relay Settings screen, change the 79 max timer to a value that is less than your 79 1TD.
Step 54. Close the breaker on the test set and wait for the RST LED to illuminate on the relay.
Step 55. Initiate a reclose sequence. The relay should go to LOCKOUT and not reclose the breaker.
Reclosing lockout LED on the relay test set and Reclosing LO LED on the relay front panel should
light.
Breaker Duty Timers
Breaker Fail Timer
Step 1.
Disable the TRIP1 and TRIP2 signals on the relay test set. Connect a voltage source to the
voltage inputs and apply a voltage that is greater than the 27 PU setting in the Relay Settings
screen for the desire settings group. Connect a current source to the current inputs and apply a
current greater than 0.5 amperes (5 ampere CT) or 0.1 ampere (1 ampere CT).
Step 2.
Close the breaker on the relay test set and wait for the RST LED on the relay to light.
Step 3.
Close the 52 TRP switch on the relay test set and measure the time from when the TRIP1
contacts close until the BFI contacts close. This time should be within 5% or 10 milliseconds,
whichever is greater of the BF TD in the INSTALLATION SETTING screen.
Slow Breaker Trip Timer
Step 4.
Disable the TRIP1 and TRIP2 signals on the relay test set. Connect a voltage source to the
Summary of Contents for BE1-DFPR
Page 10: ...BE1 DFPR General Information 1 4 Figure 1 1 Terminal Screens Flow Diagram Sheet 1 Of 2 ...
Page 11: ...BE1 DFPR General Information 1 5 ...
Page 12: ...BE1 DFPR General Information 1 6 Figure 1 2 Terminal Screens Flow Diagram Sheet 2 Of 2 ...
Page 15: ...BE1 DFPR General Information 1 9 ...
Page 23: ...BE1 DFPR General Information 1 17 ...
Page 24: ...BE1 DFPR General Information 1 18 Figure 1 4 Style Number Identification Chart ...
Page 26: ...BE1 DFPR General Information 1 20 KIWTG 6KOKPI 1RVKQP 5 5JQTV PXGTUG ...
Page 27: ...BE1 DFPR General Information 1 21 ...
Page 28: ...BE1 DFPR General Information 1 22 KIWTG 6KOKPI 1RVKQP QPI PXGTUG ...
Page 29: ...BE1 DFPR General Information 1 23 ...
Page 30: ...BE1 DFPR General Information 1 24 KIWTG 6KOKPI 1RVKQP GHKPKVG 6KOG ...
Page 31: ...BE1 DFPR General Information 1 25 ...
Page 32: ...BE1 DFPR General Information 1 26 KIWTG 6KOKPI 1RVKQP QFGTCVG PXGTUG ...
Page 33: ...BE1 DFPR General Information 1 27 ...
Page 34: ...BE1 DFPR General Information 1 28 KIWTG 6KOKPI 1RVKQP PXGTUG ...
Page 35: ...BE1 DFPR General Information 1 29 ...
Page 36: ...BE1 DFPR General Information 1 30 KIWTG 6KOKPI 1RVKQP 8 8GT PXGTUG ...
Page 37: ...BE1 DFPR General Information 1 31 ...
Page 38: ...BE1 DFPR General Information 1 32 KIWTG 6KOKPI 1RVKQP ZVTGOGN PXGTUG ...
Page 39: ...BE1 DFPR General Information 1 33 ...
Page 40: ...BE1 DFPR General Information 1 34 KIWTG 6KOKPI 1RVKQP 5 5VCPFCTF PXGTUG ...
Page 41: ...BE1 DFPR General Information 1 35 ...
Page 42: ...BE1 DFPR General Information 1 36 KIWTG 6KOKPI 1RVKQP 5 8GT PXGTUG ...
Page 43: ...BE1 DFPR General Information 1 37 ...
Page 44: ...BE1 DFPR General Information 1 38 KIWTG 6KOKPI 1RVKQP 5 ZVTGOGN PXGTUG ...
Page 45: ...BE1 DFPR General Information 1 39 ...
Page 46: ...BE1 DFPR General Information 1 40 KIWTG 6KOKPI 1RVKQP 5 QPI 6KOG PXGTUG ...
Page 47: ...BE1 DFPR General Information 1 41 ...
Page 48: ...BE1 DFPR General Information 1 42 KIWTG 6KOKPI 1RVKQP KZGF 6KOG ...
Page 50: ...BE1 DFPR Controls and Indicators 2 2 Figure 2 1 BE1 DFPR Horizontal Mount ...
Page 51: ...BE1 DFPR Controls and Indicators 2 3 ...
Page 52: ...BE1 DFPR Controls and Indicators 2 4 Figure 2 2 BE1 DFPR Vertical Mount ...
Page 57: ...BE1 DFPR Controls and Indicators 2 9 Figure 2 3 Control Module Front Panel Horizontal Mount ...
Page 59: ...BE1 DFPR Functional Description 3 2 ...
Page 60: ...BE1 DFPR Functional Description 3 3 ...
Page 61: ...BE1 DFPR Functional Description 3 4 KIWTG WPEVKQPCN NQEM KCITCO ...
Page 70: ...BE1 DFPR Functional Description 3 13 and 50TN ...
Page 85: ...BE1 DFPR Installation 4 2 ...
Page 86: ...BE1 DFPR Installation 4 3 Figure 4 1 Outline Dimensions Rack Mounting ...
Page 87: ...BE1 DFPR Installation 4 4 ...
Page 88: ...BE1 DFPR Installation 4 5 Figure 4 2 Outline Dimensions Panel Mounting ...
Page 90: ...BE1 DFPR Installation 4 7 Figure 4 3 DC Control Connections Typical ...
Page 91: ...BE1 DFPR Installation 4 8 ...
Page 92: ...BE1 DFPR Installation 4 9 Figure 4 4 Connection Diagram ...
Page 93: ...BE1 DFPR Installation 4 10 ...
Page 94: ...BE1 DFPR Installation 4 11 Figure 4 5 BE1 DFPR Rear View ...
Page 95: ...BE1 DFPR Installation 4 12 ...
Page 96: ...BE1 DFPR Installation 4 13 Figure 4 6 Communications Interface ...
Page 97: ...BE1 DFPR Installation 4 14 ...
Page 98: ...BE1 DFPR Installation 4 15 Figure 4 7 RS 232 Connection Diagram For IBM Type Computers ...
Page 100: ...BE1 DFPR Installation 4 17 Figure 4 9 RS 232 Interconnection Diagram For RFL 9660 Switch ...
Page 103: ...BE1 DFPR Testing 5 3 ...
Page 104: ...BE1 DFPR Testing 5 4 Figure 5 1 BE1 DFPR Test Simulator Front View ...
Page 105: ...BE1 DFPR Testing 5 5 ...
Page 106: ...BE1 DFPR Testing 5 6 Figure 5 2 BE1 DFPR Test Simulator Rear View ...
Page 107: ...BE1 DFPR Testing 5 7 ...
Page 108: ...BE1 DFPR Testing 5 8 Figure 5 3 BE1 DFPR Test Simulator Schematic Diagram Sheet 1 of 2 ...
Page 109: ...BE1 DFPR Testing 5 9 ...
Page 110: ...BE1 DFPR Testing 5 10 Figure 5 4 BE1 DFPR Test Simulator Schematic Diagram Sheet 2 of 2 ...
Page 111: ...BE1 DFPR Testing 5 11 ...
Page 112: ...BE1 DFPR Testing 5 12 Figure 5 5 Test Setup Diagram ...
Page 114: ...BE1 DFPR Testing 5 14 ...
Page 134: ...BE1 81 O U Maintenance 6 2 ...