METERING 

• 

True RMS measurements of voltage per phase, 
current per phase, Watts per phase and total, VARs 
per phase and total, PF, frequency,  and phase 
angle. 

• 

Energy imported, exported, and total kWh, kVARh 
and kVAh. 

• 

Measures pulses from utility pulse initiators. 

• 

Measures individual and total harmonic distortion 
on the voltage and current inputs up to the 31st 
harmonic. 

LOGGING AND RECORDING 

• 

Historical data logging of voltage per phase, current 
per phase, Watts per phase and total, VARs per 
phase and total, Power Factor, frequency and pulse 
count every 15 minutes and imported,  exported and 
total kWh,  kVARh and kVAh and total  elapsed time 
since last reset for up to 36 days*. 
OR 
Optional oscillographic recording of 12 events*, 
12 cycles each at 64 samples per cycle. 

• 

Min/Max logging of voltage per phase, current per 
phase and total,  imported,  exported, and total  kWh, 
kVARh and kVAh, and elapsed time since last reset. 

• 

Event logging and alarming with sequence of events 
time stamped to  ± 1 Omsec accuracy including 
configuration changes, set point and min/max 
events. 

History is  limited  to 

18 

days or  oscillography  is  limited  to 

events  for  the  DNP 

3.0 

option. 

CONTROL 

• 

Four non-wetted status inputs and six output relays. 

COMMUNICATION PORTS 

• 

Three independent general purpose communication 
ports. 

- Front RS-232 ASCII and TNP communications 
- Rear RS-232 TNP communications 
- Rear RS-485 Modbus™ or other common 

protocols 

• 

IRIG time sync (unmodulated) 

HARDWARE  FEATURES 

• 

Case configuration is H1  (half rack). 

• 

Active CT technology for low burden and increased 
dynamic range 

• 

Flash Memory for upgrading embedded 
programming without changing chips. 

• 

Integral HMI with 2x16 character display. 

• 

Wide range ac/dc power supply options provide 
long holdup time to ride through dips on ac power 
source.  (1 OOms with four output relays energized, 
upon complete loss of source. Starting voltage 
125Vac for Option 1  (48/125Vac/Vdc) and 250Vac 
for Option 2 (125/250Vac/Vdc)). 

APPLICATIONS 

The BE1-MMS1 00 is ideal for use by utility, industrial, 

commercial and institutional customers for feeder 
monitoring and automation, tenant sub-billing,  budget­
ary cost allocation and outage detection. Its unique 

capabilities make it ideally suited for the following 

applications: 

• 

Utility sub-metering 

• 

Commercial/Industrial metering 

• 

Substation automation 

• 

Genset applications 

And where the following is required: 

• 

A panel meter is needed to read three phase V, I, 
Watts, VARs, frequency, Watt-hours or VAR-hours. 

• 

Monitoring of energy utilizing a utility meter's pulse 
contacts. 

• 

Provisions for output contacts capable of replicating 

metering pulse contacts. 

• 

Metering data logging and the ability to communi­
cate with a central computer running SCADA 
software. 

• 

Remote or local interrogation/operation of the 
metering device. 

• 

High sample oscillographic recording. 

• 

Drawout case construction. 

UTILITY SUBSTATION  AUTOMATION 

By using one BE1-MMS1 00 on each feeder and 

connecting it to communicate with a central computer 

running SCADA software such as Basler Electric's 

UMOS©, the benefit of a complete energy manage­

ment system can be realized. The BE1-MMS1 00 
provides the system operator with real time analog 
measurements as well as historical data for planners. 
The BE1-MMS1 00 also provides the operator with 
status inputs and controllable outputs. Together, the 

BE1-MMS1 00 and  UMOS© interact through the com­

puter screens that form the operators' interface or HMI. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for BE1-MMS100

Page 1: ...ors the status of input contacts from breakers targets switches etc Provides control outputs through built in interposing relays Available in fully drawout half rack case Two Basler Electric half rack...

Page 2: ...ng chips Integral HMI with 2x16 character display Wide range ac dc power supply options provide long holdup time to ride through dips on ac power source 1OOms with four output relays energized upon co...

Page 3: ...ied from 67 or 120Vac PTs 1 2 3 or 4 ac currents supplied from 1A or 5A CTs specified at time of order Meter input signals are supplied from PTs and CTs as paired sets of input signals Input signals a...

Page 4: ...the status input channels total of four channels available Pulse repetition rates of up to 20 per second on each channel are acceptable Inputs are scanned at 10 millisecond intervals A debouncing algo...

Page 5: ...y 48 125V AC DC Serial Number XXXXXXXXXX Unit Freeze Power Status Rx Tx Display 0 0 0 0 0 BE1 MMS COM RS 232 Figure 1 Front p anel of BE1 MMS100 LCD DISPLAY USAGE The LCD display is a 16 character by...

Page 6: ...e Configuration Circuit Active Analog CT Filter Circuit Circuit ISO l ISO f ISO l ISO l Power Supply Flash Memory Ground o Chassis HMI AID LCD Circuit Display Keypad ISO ISO Microprocessor r 1 ISO I W...

Page 7: ...N1 BUS A B c N IN2 IN3 IN4 IRIG PWR GND IN4 IRIG 1 BREAKER I I I I I 07 05 03 01 A 66Jv B2 w 3 B4 v 5 B6 7 sa y y y y ISO ISO ISO ISO I Oelta Wye I A B C N LINE 7 IN IC IB 71A Configuration Circuit LJ...

Page 8: ...elay Contacts Chan 1 Output Relay Contacts Chan 2 Output Relay Contacts Chan 3 Output Relay Contacts Chan 4 Output Relay Contacts Chan 5 Output Relay Contacts Chan 6 Total Harmonic Distortion Ph a Tot...

Page 9: ...WER SUPPLY Option 1 64 cycle adjusted to input frequency 10 75Hz DC range 35 150V AC range 55 135V Option 2 Option 3 Burden OUTPUT CONTACTS Contact Current 30 Amps 10 Amps 0 3 Amps 10 Amps Operating V...

Page 10: ...vironmentalTestProcedures Part 2 Test Z AD Composite Temperature Humidity Cyclic Test Note LCD Display is inoperative below 20 C VIBRATIONI SEISMIC Qualified to IEC255 21 1 Class 1 SHOCK Qualified to...

Page 11: ...ower supply H Half rack case 3 DNP 3 0 communications jBE1 MMS100 I 1 Amp Nominal Systems 3 3 phase sensing B 1 Amp Independent Gnd Input 5 Amp Nominal Systems E 5 Amp Independent Gnd Input STANDARDAC...

Page 12: ...ND ILLINOIS U S A 62249 PAE Les Pins 67319 Wasselonne Cedex FRANCE PHONE 618 654 2341 FAX 618 654 2351 PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http www basler com info basler com Printed in U S A w...

Reviews: