BE1-MMS100
2
FEATURES
METERING
•
True RMS measurements of voltage per phase,
current per phase, Watts per phase and total, VARs
per phase and total, PF, frequency, and phase
angle.
•
Energy imported, exported, and total kWh, kVARh
and kVAh.
•
Measures pulses from utility pulse initiators.
•
Measures individual and total harmonic distortion
on the voltage and current inputs up to the 31st
harmonic.
LOGGING AND RECORDING
•
Historical data logging of voltage per phase, current
per phase, Watts per phase and total, VARs per
phase and total, Power Factor, frequency and pulse
count every 15 minutes and imported, exported and
total kWh, kVARh and kVAh and total elapsed time
since last reset for up to 36 days*.
OR
Optional oscillographic recording of 12 events*,
12 cycles each at 64 samples per cycle.
•
Min/Max logging of voltage per phase, current per
phase and total, imported, exported, and total kWh,
kVARh and kVAh, and elapsed time since last reset.
•
Event logging and alarming with sequence of events
time stamped to ± 1 Omsec accuracy including
configuration changes, set point and min/max
events.
*
History is limited to
18
days or oscillography is limited to
6
events for the DNP
3.0
option.
CONTROL
•
Four non-wetted status inputs and six output relays.
COMMUNICATION PORTS
•
Three independent general purpose communication
ports.
- Front RS-232 ASCII and TNP communications
- Rear RS-232 TNP communications
- Rear RS-485 Modbus™ or other common
protocols
•
IRIG time sync (unmodulated)
HARDWARE FEATURES
•
Case configuration is H1 (half rack).
•
Active CT technology for low burden and increased
dynamic range
•
Flash Memory for upgrading embedded
programming without changing chips.
•
Integral HMI with 2x16 character display.
•
Wide range ac/dc power supply options provide
long holdup time to ride through dips on ac power
source. (1 OOms with four output relays energized,
upon complete loss of source. Starting voltage
125Vac for Option 1 (48/125Vac/Vdc) and 250Vac
for Option 2 (125/250Vac/Vdc)).
APPLICATIONS
The BE1-MMS1 00 is ideal for use by utility, industrial,
commercial and institutional customers for feeder
monitoring and automation, tenant sub-billing, budget
ary cost allocation and outage detection. Its unique
capabilities make it ideally suited for the following
applications:
•
Utility sub-metering
•
Commercial/Industrial metering
•
Substation automation
•
Genset applications
And where the following is required:
•
A panel meter is needed to read three phase V, I,
Watts, VARs, frequency, Watt-hours or VAR-hours.
•
Monitoring of energy utilizing a utility meter's pulse
contacts.
•
Provisions for output contacts capable of replicating
metering pulse contacts.
•
Metering data logging and the ability to communi
cate with a central computer running SCADA
software.
•
Remote or local interrogation/operation of the
metering device.
•
High sample oscillographic recording.
•
Drawout case construction.
UTILITY SUBSTATION AUTOMATION
By using one BE1-MMS1 00 on each feeder and
connecting it to communicate with a central computer
running SCADA software such as Basler Electric's
UMOS©, the benefit of a complete energy manage
ment system can be realized. The BE1-MMS1 00
provides the system operator with real time analog
measurements as well as historical data for planners.
The BE1-MMS1 00 also provides the operator with
status inputs and controllable outputs. Together, the
BE1-MMS1 00 and UMOS© interact through the com
puter screens that form the operators' interface or HMI.
www
. ElectricalPartManuals