background image

BE1-MMS100 

APPLICATIONS, 

continued 

Within this interface reports can be generated and 
printed for further use. Some of the screens and 
reports provided by UMOS© are: 

SCREENS 

REPORTS 

Alarm  Panel 

Daily  Summary 

Event  Log 

Detail 

Sequence  of  Events  Log 

Volts and Amps 

Strip Charts 

On/Off  Peak 

Forecast  Strip Charts 

Monthly  Peaks 

Load  Control Schedules 

Fault 

One-line  Diagrams 

Relay  Settings 

Fault  Reports 

Oscillographic  Records 

Relay  Settings 

METERING  POWER  CONTRACTS 

A BE1-MMS1 00 can be connected on each power 
circuit and log metering data for various customers. 

Using the "call home" and dial-up modes of operation 

within the BE1-MMS1 00 and BESTCOMS software, the 

logged data can be automatically transferred at 

various intervals. 

UTILITY SUB-METERING 

The BE1-MMS1 00 and a Basler Electric BE1 protective 
relay can be dovetailed together to form a standard 19-
inch rack feeder unit for metering, protection and 

control. The combination provides the advantage of 

high metering accuracy that is normally unavailable 
within protective relays due to their wide dynamic 
range with the protection required for reliable feeder 
operation. 

COMMERCIAL/INDUSTRIAL  METERING 

The BE1-MMS1 00 can be applied anywhere a panel 

meter is needed to measure and record energy 
consumption or generation. When applied to the 
incoming feeders of buildings or areas within a facility, 
accurate data can be obtained for tenant sub-billing or 
energy consumption costing. When applied to electri­
cal machinery or equipment,  the BE1-MMS1 00 pro­
vides measurement of harmonic distortion up to the 
31st harmonic. 

FUNCTIONAL DESCRIPTION 

INPUT  SIGNALS 

CT/PT Inp ut Signals 

The BE1-MMS1 00 accepts the following input signal 
combinations: 

• 

1 ,  2 or 3 ac voltages supplied from 67 or 120Vac 

PTs 

• 

1, 

2,  3 or 4 ac currents supplied from 1 A or 5A CTs, 

specified at time of order. 

Meter input signals are supplied from PTs and CTs as 

paired sets of input  signals.  Input  signals are pro­
cessed in pairs,  with the exception of the neutral 

current input. 

The BE1-MMS1 00 samples the seven input waveforms 
at the rate of 64 samples per cycle and computes true 
RMS voltages  (3), true RMS currents  (4), and uses 
paired 1-V input samples to compute true RMS Watts 
and VARs. 

Voltage inputs are processed as either phase-to­
neutral or phase-to-phase. The voltage input configura­

tion is set via the front panel or BESTCOMS. 

New data vectors containing voltage,  current and the 

relative phase angle for 1-V pairs are available at the 

communication port once per second. The kW,  kVAR 
and frequency data are also available once per sec­
ond. The voltage, current, kW, kVAR, Power Factor 
and frequency information is displayed and updated 
on the BE1-MMS1 00 LCD display once per second. 

Once per minute the BE1-MMS1 00 computes the kWh, 

kVARh and kVAh values and displays the imported, 

exported and accumulated kWh,  kVARh and kVAh on 
the LCD display. Also,  on the minute, the BE1-
MMS1 00 computes the first 31 harmonic values for the 
voltage or current inputs and the total harmonic distor­
tion (THO%). 

Once every 15 minutes the BE1-MMS1 00 stores in flash 
memory the phase average of Volts, Amps, kW, kVAR, 

Power Factor and frequency values. The historical data 
is stored to flash memory once every 15 minutes or on 
a power down event. Flash memory will accommodate 

36 days of data storage. Data is retained for 36 days 
and is available for downloading to a master station via 
the communication port. 

Similarly, imported, exported, and accumulated kWh, 
kVARh and kVAh and elapsed time values are accu­
mulated every minute and kept in RAM, and on a 
power down event, are transferred to EEPROM. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for BE1-MMS100

Page 1: ...ors the status of input contacts from breakers targets switches etc Provides control outputs through built in interposing relays Available in fully drawout half rack case Two Basler Electric half rack...

Page 2: ...ng chips Integral HMI with 2x16 character display Wide range ac dc power supply options provide long holdup time to ride through dips on ac power source 1OOms with four output relays energized upon co...

Page 3: ...ied from 67 or 120Vac PTs 1 2 3 or 4 ac currents supplied from 1A or 5A CTs specified at time of order Meter input signals are supplied from PTs and CTs as paired sets of input signals Input signals a...

Page 4: ...the status input channels total of four channels available Pulse repetition rates of up to 20 per second on each channel are acceptable Inputs are scanned at 10 millisecond intervals A debouncing algo...

Page 5: ...y 48 125V AC DC Serial Number XXXXXXXXXX Unit Freeze Power Status Rx Tx Display 0 0 0 0 0 BE1 MMS COM RS 232 Figure 1 Front p anel of BE1 MMS100 LCD DISPLAY USAGE The LCD display is a 16 character by...

Page 6: ...e Configuration Circuit Active Analog CT Filter Circuit Circuit ISO l ISO f ISO l ISO l Power Supply Flash Memory Ground o Chassis HMI AID LCD Circuit Display Keypad ISO ISO Microprocessor r 1 ISO I W...

Page 7: ...N1 BUS A B c N IN2 IN3 IN4 IRIG PWR GND IN4 IRIG 1 BREAKER I I I I I 07 05 03 01 A 66Jv B2 w 3 B4 v 5 B6 7 sa y y y y ISO ISO ISO ISO I Oelta Wye I A B C N LINE 7 IN IC IB 71A Configuration Circuit LJ...

Page 8: ...elay Contacts Chan 1 Output Relay Contacts Chan 2 Output Relay Contacts Chan 3 Output Relay Contacts Chan 4 Output Relay Contacts Chan 5 Output Relay Contacts Chan 6 Total Harmonic Distortion Ph a Tot...

Page 9: ...WER SUPPLY Option 1 64 cycle adjusted to input frequency 10 75Hz DC range 35 150V AC range 55 135V Option 2 Option 3 Burden OUTPUT CONTACTS Contact Current 30 Amps 10 Amps 0 3 Amps 10 Amps Operating V...

Page 10: ...vironmentalTestProcedures Part 2 Test Z AD Composite Temperature Humidity Cyclic Test Note LCD Display is inoperative below 20 C VIBRATIONI SEISMIC Qualified to IEC255 21 1 Class 1 SHOCK Qualified to...

Page 11: ...ower supply H Half rack case 3 DNP 3 0 communications jBE1 MMS100 I 1 Amp Nominal Systems 3 3 phase sensing B 1 Amp Independent Gnd Input 5 Amp Nominal Systems E 5 Amp Independent Gnd Input STANDARDAC...

Page 12: ...ND ILLINOIS U S A 62249 PAE Les Pins 67319 Wasselonne Cedex FRANCE PHONE 618 654 2341 FAX 618 654 2351 PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http www basler com info basler com Printed in U S A w...

Reviews: