background image

BE1-MMS1 00 

FUNCTIONAL  DESCRIPTION, 

continued 

INPUT  SIGNALS, 

continued 

Status  and  Alarm Input Signals 

The BE1-MMS1 00 accepts the discrete input signal 

combinations on four channels. 

The inputs can be configured as pulsed  (MCD) or sus­
tained status inputs on each of the four input channels. 
The BE1-MMS1 00 requires a de contact sense voltage 
for the contacts and accepts pulses on the discrete 
input channels  (total of four channels available). The 
BE1-MMS1 00 stores ten MCD events on each input 
channel. 

Inputs are scanned at 10 millisecond intervals. A 

debouncing algorithm checks to verify that contacts 

remain closed for at least three read cycles before 

"counting" the transition as a valid pulse. 

Momentary changes of up to 20 per second are ac­
ceptable on each channel,  with provision that only the 
first ten will be stored for each channel. 

When a contact transition event occurs, the BE1-
MMS1 00 sets a status bit "on" in the communication 
port status message. The event will be detected by the 

substation computer,  RTU or master station on the 
next poll. 

For those systems incorporating dial-up communica­
tions, the event bit can trigger a "call home" communi­
cations session. In this session, the BE1-MMS1 00 dials 
a prestored telephone number and establishes a data 
communications session with the host. During this 
session, data, including the event that initiated the call, 
is uploaded from the BE1-MMS1 00 to the host. 

Puls e Inp ut Signals 

The four status inputs can be configured as pulse 
meter inputs. As a Pulse Transducer, the BE1-MMS1 00 

accepts the following input signal combinations: 1, 2,  3 

or 4 Form A or B contact inputs from a utility pulse 
initiator. 

Metering output signals (pulses) are supplied as de 
inputs from metering  KYZ contacts.  The BE1-MMS1 00 
uses de sense voltages on the contacts and accepts 
pulses on the status input channels  (total of four 
channels available). 

Pulse repetition rates of up to 20 per second on each 
channel are acceptable. 

Inputs are scanned at 10 millisecond intervals. A 

debouncing algorithm checks to verify that contacts 

remain closed for at least three read cycles before 

"counting" the transition as a valid pulse. 

Once per minute the BE1-MMS1 00 computes the 
pulse count on a per channel basis and reports the 
data via the communication port. 

Once every fifteen minutes and on power down, the 
BE1-MMS1 00 stores the total pulse count in flash RAM 
for the 15 minute interval on a per channel basis. Data 
is retained for 36 days and is available for download­
ing to a master station via the communication port. 

OUTPUT  SIGNALS 

Dis crete Outp ut Signals 

The BE1-MMS100 has six Form  "A"  output contacts for 
use in control or for pulse inputs. Pulse outputs can be 
set to represent watts, vars, pulse in 1, pulse in 2, 
pulse in 3,  pulse in 4,  or the sum of any of these. The 
maximum output pulse rate is 30 per minute. 

The relays operate on a select and operate basis. 

Communications Ports 

The BE1-MMS1 00 has three physical serial ports: 

• 

An RS-232 port on the front of the unit. 

• 

An RS-232 port on the rear of the unit. 

• 

An RS-485 port on the rear of the unit. 

The user has a choice of using either the rear RS-232 
port for data acquisition and control,  or the RS-485 

port.  The  choice  is  made  using  the 

HMI 

setup  proce­

dures. 

The BE1-MMS1 00 supports three data acquisition and 
control protocol forms  (only  applicable to the rear 
ports): 

• 

A Basler TNP data format identical to the ET V4.4 
format is used to maintain product compatibility. 

• 

Extended TNP data formats are used for the one­

minute and fifteen-minute values. 

• 

Modbus™ data formats. 

• 

DNP 3.0 data formats. 

The port supports an  8,N, 1 byte format and will 
connect at the following baud rates:  300,  600,  1200, 
2400,  4800, 9600,  and 19,200. 

DISPLAY  FEATURES 

The BE1-MMS1 00 has five (5) indicating LEOs, a 
keypad and a  LCD display. 

www 

. ElectricalPartManuals 

. com 

Summary of Contents for BE1-MMS100

Page 1: ...ors the status of input contacts from breakers targets switches etc Provides control outputs through built in interposing relays Available in fully drawout half rack case Two Basler Electric half rack...

Page 2: ...ng chips Integral HMI with 2x16 character display Wide range ac dc power supply options provide long holdup time to ride through dips on ac power source 1OOms with four output relays energized upon co...

Page 3: ...ied from 67 or 120Vac PTs 1 2 3 or 4 ac currents supplied from 1A or 5A CTs specified at time of order Meter input signals are supplied from PTs and CTs as paired sets of input signals Input signals a...

Page 4: ...the status input channels total of four channels available Pulse repetition rates of up to 20 per second on each channel are acceptable Inputs are scanned at 10 millisecond intervals A debouncing algo...

Page 5: ...y 48 125V AC DC Serial Number XXXXXXXXXX Unit Freeze Power Status Rx Tx Display 0 0 0 0 0 BE1 MMS COM RS 232 Figure 1 Front p anel of BE1 MMS100 LCD DISPLAY USAGE The LCD display is a 16 character by...

Page 6: ...e Configuration Circuit Active Analog CT Filter Circuit Circuit ISO l ISO f ISO l ISO l Power Supply Flash Memory Ground o Chassis HMI AID LCD Circuit Display Keypad ISO ISO Microprocessor r 1 ISO I W...

Page 7: ...N1 BUS A B c N IN2 IN3 IN4 IRIG PWR GND IN4 IRIG 1 BREAKER I I I I I 07 05 03 01 A 66Jv B2 w 3 B4 v 5 B6 7 sa y y y y ISO ISO ISO ISO I Oelta Wye I A B C N LINE 7 IN IC IB 71A Configuration Circuit LJ...

Page 8: ...elay Contacts Chan 1 Output Relay Contacts Chan 2 Output Relay Contacts Chan 3 Output Relay Contacts Chan 4 Output Relay Contacts Chan 5 Output Relay Contacts Chan 6 Total Harmonic Distortion Ph a Tot...

Page 9: ...WER SUPPLY Option 1 64 cycle adjusted to input frequency 10 75Hz DC range 35 150V AC range 55 135V Option 2 Option 3 Burden OUTPUT CONTACTS Contact Current 30 Amps 10 Amps 0 3 Amps 10 Amps Operating V...

Page 10: ...vironmentalTestProcedures Part 2 Test Z AD Composite Temperature Humidity Cyclic Test Note LCD Display is inoperative below 20 C VIBRATIONI SEISMIC Qualified to IEC255 21 1 Class 1 SHOCK Qualified to...

Page 11: ...ower supply H Half rack case 3 DNP 3 0 communications jBE1 MMS100 I 1 Amp Nominal Systems 3 3 phase sensing B 1 Amp Independent Gnd Input 5 Amp Nominal Systems E 5 Amp Independent Gnd Input STANDARDAC...

Page 12: ...ND ILLINOIS U S A 62249 PAE Les Pins 67319 Wasselonne Cedex FRANCE PHONE 618 654 2341 FAX 618 654 2351 PHONE 33 3 88 87 1010 FAX 33 3 88 87 0808 http www basler com info basler com Printed in U S A w...

Reviews: