There are three sub-menus under “Advance
User” setting: ELECTRONIC, BATTERY and MISCELLANEOUS.
ELECTRICAL
DATALOG
INFO
SETTING
MEASURE
CONTROL
HOME
20KVA
Bypass Mode
19:52:36
2018-11-07
ELECTRONIC
BATTERY
MISCELLANEOUS
OUTPUT VOL
OUTPUT FRE
CVCF Mode
Bypass Forbid
120V
60Hz
Disable
Disable
Electrical Setting Page 1
Output Voltage: Select the output rated voltage.
There are two options, 120V and 127V. 120Vac is default setting.
Output Frequency: Select output rated frequency.
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
CVCF Mode (constant voltage and constant frequency function)
Enable: CVCF function is enabled. The output frequency will be fixed at 50Hz or 60Hz according to
setting of “OP Freq.”. The input frequency could be from 40Hz to 70Hz.
Disable: CVCF function is disabled. The output frequency will synchronize with the bypass
frequency within 45~55 Hz for 50Hz system or within 55~65 Hz for 60Hz system. Disable is the