19
4.3.2 LCD Panel
4.3.2.1 Line mode start up
1.
Please ensure the outlet of power source is proper grounded.
2.
Ensure the voltage rating of power source is matched with UPS spec.
3.
Plug in UPS to the AC source
4.
UPS will start initializing after AC input power is available 5 seconds.
LED/LCD indicator will be all lit and dim once and fan will start spinning.
Full LCD display looks as below figure:
5.
Press UPS
button and hold untill twice beep heard, UPS begins
starting procedures for 5 seconds. LCD display will show as below figure-
A and then figure-B sequentially. LEDs
will light up to indicate that
the Utility and the Bypass are normal. And then "
","
","
LED
remain lit during figure-B LCD display.
A
B
When you see figure-B means the starting up procedure is finished. Please
ensure UPS recharge in line mode for at least 4 hours for fully recharged before the
first backup test if it’s a new installed unit.