40
9. Specifications Convertible Type (Tower)
MODEL
ITEM
BBP-AR-1000-
PSW-ONL
BBP-AR-1500-
PSW-ONL
BBP-AR-2000-
PSW-ONL
BBP-AR-3000-
PSW-ONL
CAPACITY
VA
1000 VA
1500VA
2000 VA
3000 VA
W
900W
1350W
1800W
2700W
INPUT
Voltage Rating
55/75/90-150 VAC
(Based on load percentage 0-60% / 0-75% / 0-100%)
Frequency Rating
44-66 Hz
50Hz fin< 44Hz or fin > 56Hz
60Hz fin< 54Hz or fin > 66Hz
Phase
Single phase with ground
Power Factor
≧
0.99 at full linear load
Current harmonic
distortion (THDi)
<7% at full load and nominal voltage
Generator Input
Supported
Input Connection
NEMA 5-15P NEMA 5-15P NEMA 5-20P NEMA L5-30P
Output
Voltage
*
120 V, adjustable to 100/110/115/120
Voltage Regulation
Static
:
within
±1% until low-battery warning
Frequency
(Synchronized Range)
3 Hz or 1 Hz (selectable)
Frequency
(Battery
Mode)
50/60 Hz ±0.2% unless synchronized to line
Current Crest Ratio
3:1
Voltage Harmonic
Distortion(THDv)
< 3% at full linear load
< 6% at full non-linear load
Measure Load
tolerance
±
2%
Measure voltage
tolerance
±
1%
Dynamic stability
≦
60ms/5% @ 10% to 90% Load
Output Waveform
Pure sine wave
Outlets
(6)
NEMA 5-15R
(6)
NEMA 5-15R
(6)
NEMA 5-20R
(6+1)
6*NEMA 5-20R
1*NEMAL5-30R
AC Inverter Supply
<
105
%
continuous
106-120
%
for 30 seconds transfer to bypass
121-150
%
for 10 seconds transfer to bypass
>
150
%
Immediately transfer to bypass.
Buzzer continuously alarms.
Battery Supply
<
105
%
continuous
106-120
%
for 30 seconds shuts down
121-150
%
for 10 seconds shuts down
>
150
%
Immediately shuts down.
Buzzer continuously alarms.