8.3  Status indicators (LEDs) integrated in the front panel  

The Gateway provides in the front panel four LEDs for indication of the RS485 and DeviceNet operating 
status. 
 
 

RS485 TX (yellow)

 

Transmitting a token on the RS485 sub-bus 

 
RS485 RX (yellow) 

Receiving a token on the RS485 sub-bus 

 

 
 

DeviceNet  Combined Module/Network Status LED (red and green) 

 

Status 

LED status 

Significance 

Device Not Powered/Not 
On–line 
 
 

Off 
 
 
 

Device is not on–line. 
- The device has not completed the Dup_MAC_ID test yet. 
- The device may not be powered. 
 

Device Operational AND 
On–line, Connected 
 
 
 
 

Green 
 
 
 
 
 

The device is operating in a normal condition and the device is on–
line with connections in the established state. 
- For a Group 2 Only device it means that the device is 
allocated to a Master. 
- For a UCMM capable device it means that the device has one 
or more established connections. 

Device Operational AND 
On–line, Not Connected 
or Device On–line AND 
Device needs 
Commissioning 
 

Flashing 
Green 
 
 
 
 

The device is operating in a normal condition and the device is on–
line with no connections in the established state. 
- The device has passed the Dup_MAC_ID test, is on–line, 
but has no established connections to other nodes. 
- Device is not allocated to a master. 
- Configuration missing, incomplete or incorrect. 

Minor Fault and/or 
Connection Time–Out 
and/or No Network Power 

Flashing 
Red 
 

Any one or more of the following conditions: 
- Recoverable fault 
- One or more I/O Connections are in the Timed-Out state 
- No network power present 

Critical Fault or 
Critical Link Failure 
 
 

Red 
 
 
 

The device has an unrecoverable fault; may need replacing. 
Failed communication device. The device has detected an error that 
has rendered it incapable of communicating on the network 
(Duplicate MAC ID, or Bus–off). 

Communication Faulted 
and Received an Identify 
Comm Fault Request - 
Long Protocol 

Flashing 
Red & 
Green 
 

A specific Communication Faulted device. The device has detected a
Network Access error and is in the Communication Faulted state. 
The device has subsequently received and accepted an Identify 
Communication Faulted Request - Long Protocol message. 

 
 

Summary of Contents for GK473

Page 1: ...Fax 49 0 7720 942 900 05 11 174 02 051 4 info de baumerivo com Subject to technical and design modifications www baumer com Errors and omissions excepted Manual GK473 Gateway RS485 DeviceNet Firmware...

Page 2: ...iceNet Master Slave 9 5 2 Data exchange DeviceNet RS485 sub bus 10 6 DeviceNet CIP Object Implementation 10 7 GK473 Object Class 0x64 15 7 1 Attribute 1 Autoscan SPA 16 7 2 Attribute 2 Transparent tra...

Page 3: ...ing on encoder configuration and part number delivery is including Encoder CD with describing file and manual also available as download in the Internet 1 2 Product assignment Product Product code Dev...

Page 4: ...ufacturer Safety instructions Prior to commissioning of the equipment check all electrical connections If installation e connection or any other work performed at the gateway and at the equipment is n...

Page 5: ...gateway to protective earth PE conductor using shielded cable The braided shield must be connected to cable gland or plug Ideally aim at a bilateral connection to protective earth PE i e housing via...

Page 6: ...6 7 CAN_H 8 Drain 9 RS485 utilizing the screw terminals Connection to protective earth PE is additionally provided by the DIN rail mount Gateway power supply UB 24 VDC 20 ca 50 mA Each spindle positio...

Page 7: ...erating elements are accessible The housing is closed again by pulling it back to its original position until both locks snap in again 4 3 2 Setting the DeviceNet user ID Mac ID The DeviceNet user ID...

Page 8: ...ce in the bus line the CAN bus must be terminated by resistor that is activated by setting the one pole DIP switch to ON Default OFF ON 1 ON final user OFF user X 4 3 5 EDS file For gateway projecting...

Page 9: ...unkline dropline with bilateral terminating resistors The terminating resistors provide 120 Ohm GK473 DeviceNet gateway operates as a Class 2 Slave in the DeviceNet bus network The device supports I O...

Page 10: ...art and stop token as well as CRC byte cyclic redundancy check will be taken out of the RS485 message but latter is passed with unchanged content to the data block of a DeviceNet message so that it is...

Page 11: ...ess Rule Name DeviceNet Data type Value 1 Get Vendor ID UINT 0x01D4 2 Get Device Type UINT 0x000C 3 Get Product Code UINT 0x002D 4 Get Revision STRUCT of USINT Major fieldbus version USINT Minor field...

Page 12: ...STRUCT of Allocation choice Byte Byte Master s MAC ID USINT 6 Get MAC ID Switch changed BOOL 7 Get Baud Rate Switch changed BOOL 8 Get MAC ID Switch Value USINT 9 Get Baud Rate Switch Value USINT Inst...

Page 13: ...age Groups to consume produce date 7 Get Produced Connection Size UINT 0x0030 Number of bytes transmitted across this connection 8 Get Consumed Connection Size UINT 0x0000 Number of bytes received acr...

Page 14: ...application of a RetryLimit_Reached event 3 Get Set Producing Connection Instance USINT 0x0004 Connection Instance which contains the path of the producing I O application object which will be notifi...

Page 15: ...AY 48 of USINT Information in binary code on state number and IDs of the SPAs spindle position displays connected to RS485 sub bus Byte 0 15 SPA not in position Byte 16 31 SPA in error states Byte 32...

Page 16: ...and for DeviceNet read in The AutoScan function relieves the CANopen master from proceeding cyclic SPA scanning operations itself This operating mode is necessary to make the batched information objec...

Page 17: ...message if the addressed SPA did not reply within the timeout window approx 100 ms Any timeout administered by the DeviceNet Master for monitoring of gateway reply should not be less than 400 ms The...

Page 18: ...ading the 6 digit current value bottom line of the display Data volume is always 6 Byte A negative value comes with sign 2Dh followed by 5 data Bytes Positive values are returned as 6 data Bytes less...

Page 19: ...Attribute 3 RS485 Sub bus full SPA status information Class Instance Attribute Access Rule Name DeviceNet Data type Default Value 100 1 3 Get RS485 sub bus full SPA status information ARRAY 48 of USIN...

Page 20: ...5 13 44 75 res 2 5 14 45 76 res 2 6 14 45 76 res 2 6 14 45 76 res 2 6 15 46 77 res 2 7 15 46 77 res 2 7 15 46 77 res 2 7 16 47 78 res 2 0 16 47 78 res 2 0 16 47 78 res 2 0 17 48 79 res 2 1 17 48 79 re...

Page 21: ...SPAs with identifiers 0 1 2 4 5 6 7 and 30 are connected Byte 0 15 bin r 0 31 62 93 2 0 1 32 63 94 2 1 2 33 64 95 2 2 3 34 65 96 2 3 4 35 66 97 2 4 5 36 67 98 2 5 6 37 68 bc 2 6 7 38 69 res 2 7 8 39...

Page 22: ...xample Result SPAs with identifiers 1 5 and 30 are not in position Byte 0 15 bin r 0 31 62 93 2 0 1 32 63 94 2 1 2 33 64 95 2 2 3 34 65 96 2 3 4 35 66 97 2 4 5 36 67 98 2 5 6 37 68 bc 2 6 7 38 69 res...

Page 23: ...h identifier 5 is in error state possible reason No motor supply of the motive operated SPA Byte 0 15 bin r 0 31 62 93 2 0 1 32 63 94 2 1 2 33 64 95 2 2 3 34 65 96 2 3 4 35 66 97 2 4 5 36 67 98 2 5 6...

Page 24: ...t SPAs with identifiers 1 2 4 5 and 6 are in timeout state possible reason cable break Byte 0 15 bin r 0 31 62 93 2 0 1 32 63 94 2 1 2 33 64 95 2 2 3 34 65 96 2 3 4 35 66 97 2 4 5 36 67 98 2 5 6 37 68...

Page 25: ...ected SPAs to verify whether they are existing The function Automatic SPA recognition takes for granted that all SPAs have been switched on prior to or together with the gateway 8 2 2 Cyclic scanning...

Page 26: ...or Device On line AND Device needs Commissioning Flashing Green The device is operating in a normal condition and the device is on line with no connections in the established state The device has pas...

Page 27: ...ntifier scan operation and will store all encountered identifiers in the internal memory The storing operation may take up to 14 seconds maximum Later the gateway will transmit the DUP MAC ID message...

Page 28: ...o SPA EIA RS485 ASCII Protocol Data memory 10 years flash EEPROM Programmable parameters Auto Check functions Auto Scan SPA Auto Message SPA Position Auto Message SPA Error Emitted interference DIN EN...

Page 29: ...urrent value R 52h This command is for readout of the 6 digit current value bottom line of display The amount of data is always 6 bytes In case of a negative value the sign 2Dh together with 5 data by...

Page 30: ...ata 0 RxData 1 RxData 2 RxData 3 RxData 4 RxData 5 RxData 6 RxData 7 RxData 8 RxData 9 RxData 10 RxData 11 RxData 12 RxData 13 RxData 14 RxData 15 Vendor specific Service 0x32 Class 0x64 Instance 1 At...

Page 31: ...Instance Attribute TxData 0 TxData 1 TxData 2 TxData 3 TxData 4 N20 20 TxData 5 TxData 6 TxData 7 TxData 8 TxData 9 TxData 10 TxData 11 TxData 12 TxData 13 TxData 14 TxData 15 N20 50 RX ID Status Port...

Reviews: