NE210
30
www.baumer.com
To be used
Sensor signal
Terminal assignment
- If the pulse generator is notsupplied by
the sensor powersupply from the counter.
- If the pulse generator has a push-pull or
PNP output stage.
- If several counters are triggered in
parallel by a single pulse generator.
PNP, triggered by a plus
signal.
K
E
B
11 and 12
13 12 11 10 9 8 7
- If the pulse generator has an NPN output
stage.
NPN, triggered by a
minus signal.
E
K
B
11 and 13
13 12 11 10 9 8 7
- In conjunction with a max. 24 VAC power
supply.
Alternating voltage
input: 7, 8 and 9
trggered by
max. 24 VAC.
13 12 10
11 9 8 7
Electrical isolation is provided for instruments with an AC voltage
supply and a relay output without electronic signal output in the case
of an external sensor supply.