6.1 Dimensions

6.2  Default settings

The following parameters are programmed into the counter by the 

factory prior to delivery:

Preset value, main counter P1  

100

Preset value, main counter P2  

1000

Start count value, main counter SC   0

Scaling factor, main counter XP 

1.0000

Preset value, secondary counter B1 10

Batch counter multiplier   

1

Display 

 

 

No decimal point

Pulse signal time main and 

 

secondary counters 

 

0.25 s

Operating mode 

 

Step preset

Counting mode for main and 

Track A and UP/DOWN

totalizing counter 

 

To track B

Change preset 

 

Effective after resetting

Counting frequency, main

and totalizing counters   

10 kHz

Input function, secondary counter  External triggering

Counting frequency, 

secondary counter 

 

10 kHz

Summary of Contents for NE212

Page 1: ...tellbezeichnung Baumer IVO GmbH Co KG Dauchinger Strasse 58 62 DE 78056 Villingen Schwenningen Phone 49 7720 942 0 Fax 49 7720 942 900 www baumer com info de baumerivo com Betriebsanleitung Elektronis...

Page 2: ...einwandfreiem Zustand verlassen Um diesen Ger te Status zu erhalten ist es erforderlich dass Sie das Ger t bestimmungsgem ss sicherheits und gefahrenbewusst unter Beachtung dieser Betriebsanleitung un...

Page 3: ...entsprechende Sicherheitsvorkehrungen getroffen werden ffnen Sie nicht das Geh use des Ger tes und nehmen Sie keine Ver nderungen daran vor Manipulationen am Ger t k nnen dessen Funktionssicherheit n...

Page 4: ...105 1 6 7 Aktueller Hauptz hlerstand Vorwahlwert 1 Hauptz hler Vorwahlwert 2 Hauptz hler Setzwert f r Hauptz hler XP Summenz hler Z hlerstand Nebenz hler Vorwahlwert Nebenz hler Laufender Wert des Be...

Page 5: ...er Hauptz hler mit 2 Vorwahlen Setzwert Skalierungsfaktor Nebenz hler als Vorwahlz hler mit 1 Vorwahl Multiplikator Tachometer oder Partienz hler A 90 B A B Betriebs stundenz hler B1 Ausgang P2 2 3 4...

Page 6: ...7 56 56 5 5 7 7 56 7 5 7 5 XVJDQJ 3 3 PD 9 OHPPH OHPPH OHPPH lKOXQJ 6HQVRU 9HUVRUJXQJ 131 U 313 U 5 FNVWHOOXQJ lKOHU 3 VWRS K lKOHU 3 5 FNVWHOOXQJ 1 5 7 56 5 5 7 7 56 7 5 7 5 56 5HODLV XVJlQJH OHNWURQ...

Page 7: ...ng f r Eingangslogik Sensorversorgung Sensorversorgung 21 22 Option RS485 T R Option RS485 T R 23 24 25 26 Option RS232 TxD RxD GND Option RS422 TxD TxD RxD RxD Litzenanschluss aus Gr nden des Ber hru...

Page 8: ...iessen Die Betriebsspannung nicht zur Parallelversorgung von Antrieben Sch tzen Magnetven tilen usw verwenden Die Versorgungsleitungen sind getrennt von Laststromleitungen zu verlegen Brandschutz Ger...

Page 9: ...oder PNP Schalttransistor im Werk programmiert offener Kollektor Die Ausg nge sind als Wisch oder Dauersignal in der Programmierzeile 31 32 33 programmiert Ausgangslogik Max Schaltspannung Max Schalts...

Page 10: ...legen Verwenden Sensorsignal Anwenden wenn der Impulsgeber nicht von der Sensorversorgung aus dem Z hler ver sorgt wird wenn der Impulsgeber eine Gegentakt oder PNP Endstufen hat wenn mehrere Z hler p...

Page 11: ...4V Inkrementalgeber mit PNP oder Gegentaktausgang 12 Spur A 13 Spur B 14 R ckstellung 18 PNP Br cke nach 0V 19 0V 20 24V 3 5 Sensorversorgung anschliessen Sensorversorgung an die Anschl sse 19 und 20...

Page 12: ...43 44 45 und 46 eingestellt werden Folgende Norm Schnittstellen sind an den Z hler anschliessbar RS232 RS422 RS485 Eigenschaften der Schnittstelle RS232 Vollduplex bertragung mit den Eigenschaften as...

Page 13: ...pr fen Beim Test der Ausg nge darf keine Maschinenfunktion angeschlos sen sein Test der Tastatur Test der Eing nge Die Eing nge k nnen gleichzeitig oder einzeln angesteuert wer den Die Anzeige erfolgt...

Page 14: ...D blinkt 2 ber die Taste gew nschten Parameter zur Anzeige bringen 3 Mit der 10er Tastatur neuen Wert eingeben alter Wert wird ge l scht Zur Einstellung weiterer Parameter die Schritte 2 und 3 wiederh...

Page 15: ...hler gesperrt werden Taste dr cken Summenz hler ablesen R ckstellen Taste dr cken SC Z hlerstand Nebenz hler In der Programmierebene Zeile16 kann der Z hlerstand des Ne benz hlers gesperrt werden Tast...

Page 16: ...hlt und ge ndert werden Hier werden auch die Betriebsparame ter angezeigt die in der Bedienerebene gesperrt sind Das erste Pro grammierfeld besteht aus 8 Zeilen 2 Programmierfeld Im zweiten Programmi...

Page 17: ...itigem Netzeinschalten Programmierebene Eingabe des Vorzeichens Das Einrichten der Programmierung und die 4 Programmierfelder werden nun in der Reihenfolge ihrer Anwendung beschrieben Programmierung e...

Page 18: ...Zeile 4 SC SC Setzwert des Hauptz hlers Zeile 5 SC Summenz hler Zeile 6 SC XB Z hlerstand Nebenz hler Zeile 7 SC B1 Vorwahlwert Nebenz hler Zeile 8 SC Betriebsstundenz hler Nach Ablauf des ersten Pro...

Page 19: ...sprungen Die entsprechende Funktion bleibt erhalten Status ndern Entsprechende Status Zahl mittels Zehnertastatur eingeben Ge nderte Status Zahl wird automatisch abgespeichert wenn die n chste Progra...

Page 20: ...ederholt Taste dr cken Die Programmierzeilen werden nacheinander angew hlt Die Eingabe wird abgespeichert wenn die n chste Programmierzeile abgerufen wird Zeile 21 Betriebsarten 0 Stufenvorwahl 1 Haup...

Page 21: ...ckstellung und extern flankenaktiv 2 nur externe R ckstellung statisch wirksam 3 nur externe R ckstellung flankenaktiv Zeile 30 R ckstellung Nebenz hler 0 Automatische R ckstellung und extern statisch...

Page 22: ...Eingabe der Messzeit in Sekunden s 0 Zeitbasis 1 s 1 Zeitbasis 2 s 2 Zeitbasis 3 s 3 Zeitbasis 6 s 4 Zeitbasis 10 s 5 Zeitbasis 20 s 6 Zeitbasis 30 s 7 Zeitbasis 60 s Die Zeitbasis in Anh ngigkeit von...

Page 23: ...9 Zeile 46 Stoppbits 0 1 Stoppbit 1 2 Stoppbits Die Strichlinie stellt das Ende des vierten Programmierfeldes dar Programmierung Taste dr cken ausschalten l Z hler befindet sich in der Bedienerebene Z...

Page 24: ...etriebsstundenz hler 20 Trennzeile Programmierfeld 3 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 Betriebsarten Hauptz hler Skalierungsfaktor Hauptz hler Multiplikator Nebenz hler Fr...

Page 25: ...alten die Ausg nge als Dauersignale bei berschreiten des jeweiligen Vorwahlwertes in beide Z hlrichtungen Diese k nnen beliebig gew hlt werden und arbeiten unabh ngig voneinander Wischsignale sind bei...

Page 26: ...h die keine Auswer tungselektronik beinhalten und kein Z hlsignal nebst zuge h rigem Z hlrichtungssignal liefern Spur A Spur B Z hlung 4x Z hlung 2x Z hlung 1x 5 3 Ausgangsverhalten Output modes Das V...

Page 27: ...2 Tw RESET VW P1 VW P2 O OUT 1 OUT 2 SC Stufenvorwahl mit Wischsignal mit Vorkontakt als Dauersignal mit automatischer R ckstellung Setzwert negativ RESET VW P2 VW P1 O OUT 1 OUT 2 SC Tw RESET VW P1 V...

Page 28: ...zwert bei Null RESET VW P2 VW P1 O OUT 1 OUT 2 Tw Tw RESET VW P1 VW P2 O OUT 1 OUT 2 SC Tw Tw Parallelvergleich RESET VW P2 VW P1 O B1 OUT 1 OUT 2 Bei subtrahierender Betriebsart ist kein sinnvoller B...

Page 29: ...er Tachometer Betriebsstundenz hler Ziffernh he 7 6 mm Funktion Vorwahlz hler Hauptz hler mit 2 Vorwahlen Nebenz hler mit 1 Vorwahl Summenz hler Betriebsstundenz hler Skalierungsfaktor 0 0001 9999 99...

Page 30: ...x 68 mm 0 7 Werkstoffe Geh use Makrolon 6485 PC Frontfolie Polyester Masse ca 320 g 24 VDC 85 265 VAC 450 g 24 48 VAC Technische Daten Schaltpegel Optokoppler Eing nge Eingangsschaltung Steuereing nge...

Page 31: ...gsfaktor Hauptz hler XP 1 0000 Vorwahlwert Nebenz hler B1 10 Nebenz hler Multiplikator 1 Anzeige Ohne Dezimalpunkt Wischsignalzeit Haupt Nebenz hler 0 25 s Betriebsart Stufenvorwahl Z hlweise f r Haup...

Page 32: ...oher Z hlfrequenz Z hlfrequenz f r Spur A oder B zu hoch Z hlfrequenz f r Nebenz hler zu hoch Fehlermeldung bis k nnen mit Taste gel scht werden 7 Bestellbezeichnung NE212 AX A2 Betriebsspannung 1 24...

Page 33: ...ly 40 Assignment signal output relay 40 Assignment electronic output 41 Assignment signal input 41 Typical connections 43 Connecting the sensor supply 43 Connecting the interfaces 44 Executing the tes...

Page 34: ...ate and in safe condition To keep the units in this condition it is necessary that the units be installed and operated properly in a safety and hazard conscious manner under observance of this operati...

Page 35: ...sks or a danger of property or environmental damage could result then appropriate safety precautions must be taken Do not open the housing of the units or make any changes to it Tampering with the uni...

Page 36: ...8 105 1 6 7 Current main counter status Preset value 1 main counter Preset value 2 main counter Start count main counter XP Totalizing counter Counter status batch counter Preset value batch counter C...

Page 37: ...Main counter with 2 presets start count scaling factor Batch counter as preselection counter with 1 preset multiplier tachometer or batch counter A 90 B A B Operating time meter B1 Output P2 2 3 4 5...

Page 38: ...RXQW 6HQVRU VXSSO 131 U 313 U UHVHW FRXQWHU 3 VWRS K FRXQWHU 3 UHVHW 1 5 7 56 56 5 5 7 7 56 7 5 7 5 2XWSXW 3 3 PD 9 WHUPLQDO WHUPLQDO WHUPLQDO RXQW 6HQVRU VXSSO 131 U 313 U UHVHW FRXQWHU 3 VWRS K FRXQ...

Page 39: ...1 22 Option RS485 T R Option RS485 T R 23 24 25 26 Option RS232 TxD RxD GND Option RS422 TxD TxD RxD RxD For protection against shock hazards as specified in EN 61010 stran ded conductors may only be...

Page 40: ...uti lize the voltage supply for parallel supply of drives shields magnetic valves etc Supplying lines must be separated from lines providing load current Fire protection Operate the instrument using t...

Page 41: ...ogrammed by the factory as NPN or PNP switching transistors open collectors in accordance with purchase order specification The outputs are programmed as pulse or continuous signals in the programming...

Page 42: ...be used Sensor signal Terminal assignment If the pulse generator is not supplied by the sensor powersupply from the counter If the pulse generator has a push pull or PNP output stage If several count...

Page 43: ...jumper to 24V 19 0V 20 24V Incremental encoder with PNP or push pull output 12 track A 13 track B 14 reset 18 PNP jumper to 0V 19 0V 20 24V 3 5 Connecting the sensor supply Connect the sensor supply...

Page 44: ...following standard interfaces can be connected to the counter RS232 RS422 RS485 Interface characteristics RS232 Full duplex transmission with the following characteristics Asymmetric Three leads Point...

Page 45: ...puts outputs and interface in sequence No machine functions may be connected when the outputs are tested Keyboard test Input test Inputs can be triggered simultaneously or individually A display is on...

Page 46: ...ppears on the display 3 Enter new parameter by the 10 figure keypad the old parameter will be deleted To enter more parameters repeat steps 2 and 3 4 Confirm the entered parameter by pressing the key...

Page 47: ...izing counter can be disabled in the programming mode line 15 Press the key Read the totalizing counter Reset Press the key SC Batch counter status The batch counter status can be disabled in the prog...

Page 48: ...rs which are disabled in the operating mode are also displayed here The first programming segment consists of 8 lines Programming field 2 In the second programming field the individual operating param...

Page 49: ...e time Operating Programing mode Input of a sign The method of accessing the programming mode is described be low together with the four programming segments in the order in which they are used To acc...

Page 50: ...e 4 SC SC Main counter start count value Line 5 SC Totalizer Line 6 SC XB Batch counter status Line 7 SC B1 Batch counter preset value Line 8 SC Time meter After the conclusion of the first programmin...

Page 51: ...evel The respective function however remains To change status Input the appropriate status number via the numerical keypad The changed status will automatically be stored when the next programming lin...

Page 52: ...ming lines are displayed in succession The input is stored when the next line is called up Line 21 Operating modes 0 Step preset 1 Main presets 2 Parallel comparison 3 P1 Self adjusting preset Line 22...

Page 53: ...ve 1 Automatic reset and external edge active 2 External reset only statically effective 3 External reset only edge effective Line 30 Reset batch counter 0 Automatic reset and external statically effe...

Page 54: ...asurement in seconds s 0 Time base 1 s 1 Time base 2 s 2 Time base 3 s 3 Time base 6 s 4 Time base 10 s 5 Time base 20 s 6 Time base 30 s 7 Time base 60 s The time base must be selected in accordance...

Page 55: ...its At the conclusion of these programming lines a broken line will appear in the display signifying the completion of the fourth pro gramming segment To leave the Press the key programming mode l Cou...

Page 56: ...value STAT Time meter 20 Separating line Programming field 3 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 Operating modes main counter Scaling factor main counter Multiplier batch c...

Page 57: ...value in either counting direction is exceeded Any preset value can be chosen they are processed independently of each other Pulse signals cannot be given in the parallel comparison modes P1 Self adj...

Page 58: ...luation One two or fourfold evaluation is possible Track A Track B Counting 4x Counting 2x Counting 1x 5 3 Output responses output modes Signal output response is determined by the following Programm...

Page 59: ...VW P1 VW P2 O OUT 1 OUT 2 SC Step preset with pulse signal but preliminary contacts as continuous signal with auto matic reset with minus start count value RESET VW P2 VW P1 O OUT 1 OUT 2 SC Tw RESET...

Page 60: ...alue at zero RESET VW P2 VW P1 O OUT 1 OUT 2 Tw Tw RESET VW P1 VW P2 O OUT 1 OUT 2 SC Tw Tw Parallel comparison RESET VW P2 VW P1 O B1 OUT 1 OUT 2 Operation in the subtracting mode is impractical Self...

Page 61: ...our counter Digit height 7 6 mm Function Preset counter Main counter with 2 presets Batch counter with 1 preset Totalizer Hour counter Scaling factor 0 0001 9999 99 Multitplier batch counter 1 99 Coun...

Page 62: ...8 mm 0 7 Materials Housing Makrolon 6485 PC Keypad Polyester Weight approx 320 g 24 VDC 85 265 VAC 450 g 24 48 VAC Technical data Trigger level Optocoupler inputs Input circuit Control inputs PNP NPN...

Page 63: ...tor main counter XP 1 0000 Preset value secondary counter B1 10 Batch counter multiplier 1 Display No decimal point Pulse signal time main and secondary counters 0 25 s Operating mode Step preset Coun...

Page 64: ...s at high counting frequency Counting frequency for track A or B too high Counting frequency for batch counter too high Error messages and can be cleared with the key 7 Part number NE212 AX A2 Supply...

Reviews: