34
3.4
3.4.3
Electrical data - BM4163
1)
All rated values refer to a mains input voltage of 400 V / 50 Hz and a control voltage of 24 V.
2)
Effective value at an environmental temperature of 40 °C.
3)
Between 40 °C and 55 °C the output current must be reduced.
The permitted output current (I
0
) is calculated with the following formula:
BM41
63
Input rated power
1)
162 kVA
Input rated current
1)2)3)4)
(I
eff
)
235 A
Input peak current (I
eff
)
1)2)4)5)
305 A
PWM switching frequency
8 kHz
DC link voltage
640 V
DC
to 760 V
DC
DC link capacity (internal)
6000
µ
F
DC link capacity (external), permitted
max. 14 mF
DC link discharging time (internal DC link capacity)
130 s
Output power DC link
1)6)
max.150 kW
Peak power DC link
7)
195 kW
Max. peak power time
5)
60 s
Power factor (only inductive)
0,9 to 1,0
Switch-on frequency
v
2 min,
see
Max. charging time
b
30 s
Fast discharge
b
5 s
Chopper current, permitted (Î)
max. 230 A
Chopper resistor external
v
3,4
Ω
Chopper on voltage (Û)
814 V
Chopper peak power
179 kW
Permitted chopper continuos power
130 kW
Power loss related to mains connection
8)
5300 W
Power loss related to control voltage
max. 80 W
Power loss of fan related to 230 V
AC
9)
174 W
Cooling air requirement power heatsink
400 m
3
/h
Cooling air requirement internal space of device
200 m
3
/h
I0 I0 40°C
(
)
1
Coolant temperature - 40 °C
°C
------------------------------------------------------------------------------
0 03
,
⋅
–
⋅
=
Summary of Contents for b maXX 4100 Series