Mains filters
Operation manual
b maXX
BM4100 (NWR)
Document no.: 5.04052.09
Baumüller Nürnberg GmbH
118
11.3
11.3 Mains filters
Each device needs a mains filter to comply with the recommended limit values of the EMC
regulation.
11.4 Surge protection module
A surge protection module BFO-3-550-00 (article number 386058) is mandatory in every
application .
The module must be connected as follows:
Figure 46:
Connection surge protection module
Device
Input rated
current
Input peak
current
Schaffner filter
www.schaffner.com
BM4135
55 A
82,5 A
FN 3120H-80-35
BM4145
125 A
162,5 A
FN 3120H-150-40
BM4163
300 A
340 A
FN 3100-300-99
bis 2013
ab 2014
BFO-3-550-
000
BFO-3-550-
001
Summary of Contents for b maXX 4100 Series
Page 143: ......