Design and Operation
Operation manual
b maXX
BM4100 (NWR)
Document no.: 5.04052.09
43
4
4.6
Marking of the function modules - type key
On the front sheet you will find the type key of the plug-in module.
4.7
UL notes
m
Requirements to the connecting cables
n
Use 60 °C/75 °C copper wire only for all devices
n
Use Class 1 wire only.
m
n
Note tightening torque for connection terminals.
m
Required environmental conditions
n
Use the device only in a pollution degree 2 environment
n
Observe the maximum environmental temperature and the derating
m
Requirements to the energy supply / supply system
n
For use on a solidly grounded wye source only
n
The control circuit shall be supplied by an isolated power supply or control trans-
former rated max. 42.4 V peak, 10,000 VA.
m
n
BM4135 may also be protected with Type E self protected combination motor con-
troller, sized based on the rated current
n
Converters may be used with listed fuses or listed circuit breakers DIVQ as overcur-
rent protection.
cUL notes
Additional only for Canada:
NOTE
This type key is valid only for permanently installed function modules of the series
b
maXX 4100
. Other plug-in modules have an own type key.
BM4
- F -
XXX - XX
Device family, in which the plug-in module can be build in
BM4 -
F
-
XXX - XX
Plug-in module type (function module)
BM4 - F -
XXX
- XX
Plug-in module identification
SEA:
SRM:
UME:
DIO:
Main contactor control module
Main contactor monitoring module
Mains voltage sensing module
Digital I/O module
NOTE
Overvoltage Protection Device have to be installed in front of the input circuit of the
device to limit the maximum overvoltage peak to 2.5 kV.