Technical Data
Instruction handbook Mains filters
BFN
Document No.: 5.09010.03
29
3
3.4.1
Filters for TN/TT-systems
BFN 3-1-... -001
0007
0016
0030
0042
0056
0075
0100
0130
0180
Max.
supply voltage
3 x 480 V
AC
+10 %,
50/60 Hz
Rated current
(at T
B
=
50 °C)
7 A
16 A
30 A
42 A
56 A
75 A
100 A
130 A
180 A
Peak current
(at T
B
= 50 °C)
1,5 x I
N
for < 1 min à hour
Current derating
I
I
rated
85
environment
35°C
----------------------------------
–
=
Test voltage
Cable - Cable: 2125 V
DC
/ 2 s
Cable - Cabinet: 2125 V
DC
/ 2 s
Connection
L1/L2/L3: safe-to-touch screw contact
PE-Connection: Bolt M5 / M6 / M10
Maximum
connection cross-sec-
tion
4
mm
2
4
mm
2
10
mm
2
10
mm
2
16
mm
2
25
mm
2
50
mm
2
50
mm
2
50
mm
2
Power loss (typical)
4 W
8 W
12 W
15 W
18 W
24 W
24 W
30 W
35 W
Protection class
IP 20
EPCOS
B84143A0150R410
Max.
supply voltage
3 x 480 V
AC
+10 %,
50/60 Hz
Rated current
(at T
B
=
50 °C)
150 A
Peak current
(at T
B
= 50 °C)
1.5 x I
N
for < 3 min per hour
2,5 x I
N
for < 30 s per hour
Test voltage
Cable - Cable: 2240 V
DC
/ 2 s
Cable - Cabinet: 2720 V
DC
/ 2 s
Connection
L1/L2/L3: safe-to-touch screw contact
PE: Bolt M10
Maximum
connection cross-sec-
tion
95 mm
2
Protection class
IP 20
Summary of Contents for BFN 3-1 Series