Electrical data
Instruction handbook Mains filters
BFN
Document No.: 5.09010.03
Baumüller Nürnberg GmbH
28
3.4
3.4
Electrical data
DANGER!
Danger to life due to high discharge current!
Therefore:
m
The cross-section of the protective conductor must be at least 10 mm
2
(EN 61800-
5-1 chap. 4.3.5.5.2).
NOTE!
Rated current of used filters must be greater or the same with the RMS values of the
actual mains current (actual mains current = RMS value of the mains current during
the total cycle time of the drive). The RMS value is calculated at short-time operation
(S3) as follows:
I
eff
1
T
---
i
2
0
T
dt
=
Summary of Contents for BFN 3-1 Series