System requirements with regard to EMC-stability
Instruction handbook Mains filters
BFN
Document No.: 5.09010.03
Baumüller Nürnberg GmbH
50
7.5
m
Use mains filters recommended by Baumüller
m
Observe the correct sequence of the components:
Mains - fuse - mains filters - power choke (dependent of power converter) - power con-
verter - motor
m
If Baumüller motor cables and - components are used only, the compliance with the
permitted limit value of the interference immunity and of the interfering radiation can be
assumed.
m
The maximum length of the motor cable is limited. The length is dependent of the
cross-section of the cable (for example 100 m at 1.5 mm
2
, 30 m at 35 mm
2
). The max-
imum length should be reduced by the factor 1/n, if n-parallel-connected motor cables
are used.
m
The screened motor cable between the power converter and the motor must be one
piece. The cable may not be interrupted by terminals, contactors, fuses etc.
m
The smallest possible effective height is reached, if the cable is installed bonded face-
to-face on the surface of grounded switching device panels
Figure 14:
Cable installation - effective height
m
The cables shall be installed as near as possible to the conductors of the grounded
system. Herewith effective loop area for the magnetic coupling is reduced.
Figure 15:
Cable installation - loop area