Commissioning
BUG 3/2/20 Basic Feed Unit
41
Baumüller Nürnberg GmbH
5.96064.02
6 C
OMMISSIONING
WARNING
Plants that have drive converters installed, must have additional monitoring and protection devices
according to the respective regulations, e.g. technical equipment regulations, safety precautions etc.
Alterations of the drive converters or the operation software are prohibited.
This equipment carries a dangerous voltage and contains dangerous rotating parts (fans). Ignoring the
safety and warning information may result in death, severe personal injury or damage to property.
Only qualified personnel which has been instructed with all safety-related information as well as the
mounting-, service- and maitenance instructions given in this document is allowed to operate this de-
vice.
You are responsible for mounting the Mono power unit, the motor and any other equipment in accor-
dance with appropriate safety regulations (e.g. DIN, VDE); equally, you must ensure that all other
relevant national and local regulations are met with regard to cable ratings and protection, grounding,
disconnectors, overcurrent protection, etc.
The most important factors for protecting people are the DIN/VDE protective measures and safety
regulations. If there are no protective earth connections on the equipment, commutating reactor or the
motor, personal injuries are inevitable, since the surfaces may carry dangerously high voltages.
The mains unit and the field connector of the power converter carry a dangerous voltage even when
the main contactor has dropped. Do not touch these modules when under power. Connect test equip-
ment only in powerless state!
After the drive converter is separated from the power supply you must not touch any connectors as
they still might carry dangerous loads. Observe the waiting time given on the danger sign information
on the drive converter.
During operation, the principles on which the power converter and the motor work lead to leakage
currents to earth that are dissipated via the specified protective earths and may result in a current-
operated e.l.c.b on the input side blowing prematurely.
In the case of a short-circuit to frame or to ground, a direct proportion may arise in the leakage current
that makes triggering a higher level current-operated e.l.c.b. either more difficult or totally impossible.
The connection of the converter to mains using only an e.l.c.b. is prohibited (refer to pr EN
50178:1994 section 5.2.11.2 and appendix A 5.2.11.2 diagram 7).
Before carrying out commissioning, check whether the plastic covers over the power stage connec-
tions are in place.
The appliances are only to be operated on earthed mains systems.
The discharge time of the power conducting parts is more than 1 minute.
Summary of Contents for BUG 2
Page 8: ...Abbreviations IV BUG 3 2 20 Basic Feed Unit 5 96064 02 Baumüller Nürnberg GmbH ...
Page 12: ...Safety Information 4 BUG 3 2 20 Basic Feed Unit 5 96064 02 Baumüller Nürnberg GmbH ...
Page 20: ...Transport Unpacking 12 BUG 3 2 20 Basic Feed Unit 5 96064 02 Baumüller Nürnberg GmbH ...
Page 48: ...Installation Accessories 40 BUG 3 2 20 Basic Feed Unit 5 96064 02 Baumüller Nürnberg GmbH ...