Installation
38
Basic Supply Unit BUG 622, 623
5.94034.07a
Baumüller Nürnberg GmbH
y
Ba+, Ba-
Ballast resistance terminal on a basic supply unit BUG 622, 623 with "external ballast".
M 6 terminals
If UL508C has to be observed:
Use 60°C / 75° C copper conductors only (UL508C, Nov 27, 1996,
Tab. 39.2).
Nominal tightening torque of the terminal screws: 4 Nm resp. 35,4 pound-inches.
WARNING
A resistance lower than 16
Ω
are not permitted, as this may cause damage to the equipment.
The power of the external ballast resistance depends on the motor and is not monitored by the unit.