Safety Notes
Basic Supply Unit BUG 622, 623
5
Baumüller Nürnberg GmbH
5.94034.07a
1
Safety Notes
Foreword
Relatively high leakage to earth occurs in the converter and the motor, i.e. the drive may be incompati-
ble with residual current protective devices. During operation, the principles on which the converter and
motor work, lead to leakage currents to earth which are dissipated via specified protective earth con-
nections and which may result in a current-operated e.l.c.b. on the input side blowing prematurely.
A DC component in the fault current may occur in the event of a short-circuit to frame or earth fault
which makes a triggering of the higher-level current-operated e.l.c.b. more difficult or even impossible.
The connection of the current controller to the mains using only the current-operated e.l.c.b. is
prohibited (EN 50178 / VDE 0160 /11.94, sections 5.2.11 and 5.3.2.1)
The units are protected against direct contact by being installed into common switching cabinets which
meet the minimum protection requirements according to EN 50178 / VDE 0160 / 4.98, section 5.2.4.
Sheets of plastic covering the control electronics, the power stage and the device connection,
additionally prevent accidental contact during commissioning and casual use of control elements
located close to the equipment (DIN VDE 0106 Part 100, Accident Prevention Regulation VBG4
”Electrical Systems and Equipment).
The protective measures and safety regulations according to DIN/VDE are binding for personal
security.
Neglecting to fit PE connections on the equipment or the motor will result in serious personal injury and/
or considerable damage to material assets.
It is only permitted to use the devices on earth-protected supply mains.
The discharge time of live parts is > 1 min. and depends on the connected DC link capacity.
This devices are not short-circuit-proof.
General Notes
This manual contains the necessary information for normal operation of the products described therein.
It is intended for technically-qualified personnel who are specially trained and are familiar in detail with
all warnings and maintenance tasks.
The units are finished to the highest standard and are safe and reliable. They can be installed and oper-
ated safely, and function without problem if the following cautionary notes in this manual are observed.
DANGER
Due to the nature of electrical equipment, certain parts of this unit carry dangerous voltage during
operation.
Serious injury and/or damage to property can result from non-compliance with these safety notes
and warnings.
Only qualified personnel familiar with the safety instructions, and instructions regarding assembly,
maintenance and operation are to work on this unit.
Summary of Contents for BUG 622
Page 1: ...E 5 94034 07a Manual Basic Supply Unit BUG 622 623 ...
Page 8: ...Safety Notes 8 Basic Supply Unit BUG 622 623 5 94034 07a Baumüller Nürnberg GmbH ...
Page 16: ...Technical Data 16 Basic Supply Unit BUG 622 623 5 94034 07a Baumüller Nürnberg GmbH ...
Page 20: ...Assembly 20 Basic Supply Unit BUG 622 623 5 94034 07a Baumüller Nürnberg GmbH 4 1 Dimensions ...
Page 50: ...Maintenance 50 Basic Supply Unit BUG 622 623 5 94034 07a Baumüller Nürnberg GmbH ...
Page 57: ......