Installation
Operation Manual
Safety I/O Terminals
SI4000 / SO4000
Document no.: 5.08009.05
Baumüller Nürnberg GmbH
48
7.1
7.1.8
Parameterization
7.1.8.1 SI4000 parameter overview
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
7
...
...
...
...
...
...
...
...
...
...
...
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
1023
WARNING!
Unique safety address
Each address may only be used once within a network!
Dip switch
Address
1
2
3
4
5
6
7
8
9
10
PrmName
Meaning
Values
S_Address
Dip switch address
1 to 1023
Channel 1
Activation of channel 1
active/not active
Channel 2
Activation of channel 2
active/not active
Channel 3
Activation of channel 3
active/not active
Channel 4
Activation of channel 4
active/not active
Sensor test
channel 1
The clock signal for connection
is checked at connection Input1-
active/not active
Sensor test
channel 2
The clock signal for connection
is checked at connection Input2-
active/not active
Sensor test
channel 3
The clock signal for connection
is checked at connection Input3-
active/not active
Sensor test
channel 4
The clock signal for connection
is checked at connection Input4-
active/not active
Channel 1 and
2
For two-channel evaluation, inputs 1 and 2
must have the same signal states
single-channel evalua-
tion/two-channel evalu-
ation