7.2.1.3 Diag 3 (red) and Diag 4 (red)
The Diag 3 and Diag 4 LEDs indicate internal terminal errors.
NOTICE!
Returning the terminal
These errors lead to shutdown of the terminal. The terminal must be checked by Bau-
mueller Anlagen-Systemtechnik GmbH & Co. KG.
Diag 3 LED (red)
Diag 4 LED (red)
Source of error
Lit
flashes (see below for
flashing codes)
µC1
Lit
off
µC2
In the event of a fault the Diag 4 LED indicates the type of error through flashing codes.
The flashing codes are structured as follows:
Flashing sequence
Meaning
Rapid flickering
Start of flashing code
First slow sequence
Error code
Second slow sequence
Error code argument
Figure 14:
Blinking sequence
Count the number of flash pulses after the rapid flickering sequence
m
during the first slow sequence in order to ascertain the error code
m
during the second slow sequence in order to ascertain the error argument
The flashing code is repeated after the second slow sequence, followed by rapid flicker-
ing.