Cable testing
Syscompact 2000 M pro
50 / 98
822-175-2
11.3 Performing the cable test
11.3.1 Safety instructions for cable testing
WARNING
Risk of arcing faults and noise that can damage hearing as a result
of cable breakdown during testing.
Danger to life as a result of electric shock, burns, electro-ophthalmia,
hearing damage.
Use suitable personal protective equipment against electric shocks
and arcing faults.
Use ear protection.
Keep a safe distance from the connection point of the test object
according to the nominal voltage of the network.
NOTICE
The device may be damaged by an excessive output current
An excessive output current during DC voltage mode can generate high thermal
loads. This will damage the transformer.
When using DC voltage mode, observe the maximum permissible output current.
Further information: Chapter
Maximum permissible output current in DC voltage
mode
(on page 15)
11.3.2 Prerequisites
The test area is secured.
The test object is connected properly.
Further information: Chapter
Commissioning
(on page 33)
The parameters are set.
Further information: Chapter
Setting the test parameters on the system control panel
(on
page 49)