4.11
In the United Kingdom, as supplied, this appliance can be installed in the
following situations: -
Note: A spigot extension is available (Baxi Fires Division part number 0595191). When
fitted this shall extend through the closure plate for at least 15mm and have a minimum
clearance of 50mm from the end to any surface.
4.11.1
The appliance must be mounted on a non-combustible hearth
except when the
conditions in section 4.11.3 are met
(N.B. conglomerate marble hearths are considered
as non-combustible). The hearth must be at least 680mm wide x 300mm deep. The
hearth material must be at least 12mm thick. The periphery of the hearth (or fender)
should be at least 50mm above floor level to discourage the placing of carpets or rugs
over it.
The appliance can be fitted to a purpose made proprietary class “O” 150°C surround.
4.11.2
Conventional fireplace.
The fireplace opening must be within the following dimensions:
*
The total height of the closure plate is 660mm and will accommodate a maximum
opening height of 650mm (This allows a 10mm overhang). Heights above
635mm (Inclusive of sealing tape) will leave the sealing tape and closure plate visible
above the appliance.
4.11.3
Wall mounting to conventional or pre-cast flues.
The wall opening must be within the following dimensions:
*
The total height of the closure plate is 660mm and will accommodate a maximum
opening height of 650mm (This allows a 10mm overhang). Heights above
635mm (Inclusive of sealing tape) will leave the sealing tape and closure plate visible
above the appliance.
The bottom of the appliance must be at least 100mm above the finished floor covering.
See figure 1. This requires the top of the opening to be at least 650mm above the
Page 11
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2007.
Width
Height
Max.
432mm
Min.
305mm
Max.
610mm*
Min.
550mm
Width
Height
Max.
432mm
Min.
305mm
Max.
610mm*
Min.
334mm