9.8 To remove the complete burner module, pipes and pilot.
9.8.1
Remove the fascia as section 9.2.
9.8.2
Remove the ceramic fuel effect as section 9.3.
9.8.3
Support the inlet ‘T’ connector to avoid straining the pipework and disconnect the
appliance.
9.8.4
Detach the gas tap bracket from the right side of the appliance by removing three
screws (See figure 15).
9.8.5
Detach the left side of the burner from the firebox by removing one screw (See
figure 15).
9.8.6
Free the burner & pilot module from the rear pilot air pipe and the firebox by
carefully sliding the module to the right while pulling it slightly (See figures 15 and 16).
9.8.7
Remove the pipes, or pilot unit if required.
9.8.8
Replace in the reverse order.
Note:
1.
The pilot unit is an atmosphere sensing device. It must be replaced as a
whole assembly. Its individual components are not separately replaceable.
2.
If the pilot is removed, when refitting, make sure that the pilot heat shield is
in place between the pilot unit and the rear of the burner and is the correct
way round (See figure 16).
3.
Check that there is no blockage of the air intake tube at the back of the pilot
unit. Make sure that the air intake tube locates fully into the pilot air pipe
attached to the back panel (See figure 16).
Page 26
INSTALLER GUIDE
©
Baxi Heating U.K. Limited 2007.
Figure 16. Pilot air pipe location