10. FULL OPERATING CHECKS
Spillage check.
For installations without the 'Liberty' casting
!
A spillage check must be made before
leaving the installed appliance with the
customer. Make this with all the ceramic fuel
effect pieces and firefronts / castings are in
position. (See figure 16 )
For installations with the 'Liberty' casting
!
A spillage check must be made before
leaving the installed appliance with the
customer. Make this with all the ceramic fuel
effect pieces and firefronts / castings are in
position. (See figure 17)
!
Close all doors and windows in the room
containing the appliance. Light the appliance
and set the control to the
‘HIGH’ position. Leave the
appliance on for five minutes.
See lighting instructions
within section 7 of this guide.
!
The end of the smoke
match should be level with the
front face of the fireplace
opening.
!
The installation is
satisfactory if the smoke is
drawn into the fireplace
opening. If the smoke is not
drawn into the fireplace
opening, leave the appliance
alight at the maximum setting
for a further ten minutes and
then repeat the test. If smoke
is still not drawn into the appliance
disconnect the appliance and seek expert advice.
Page 20
INSTALLER GUIDE
Figure 17. Spillage check for installation with the
‘Liberty’ casting
Figure 16. Spillage check